A homeowner installs an double-pane insulating glass window of dimensions 1.20 m×1.50 m1.20\text{ m}\times 1.50\text{ m}. The unit consists of two glass panes, each of thickness Lg=4.00 mmL_g = 4.00\text{ mm} and thermal conductivity kg=0.800 W/(m⋅K)k_g = 0.800\text{ W}/(\text{m}\cdot\text{K}), separated by a stagnant air gap of thickness La=12.0 mmL_a = 12.0\text{ mm} and thermal conductivity ka=0.0260 W/(m⋅K)k_a = 0.0260\text{ W}/(\text{m}\cdot\text{K}). The interior room air is at Tin=22.0∘CT_{\text{in}} = 22.0^{\circ}\text{C} with an indoor convection coefficient hin=7.50 W/(m2⋅K)h_{\text{in}} = 7.50\text{ W}/(\text{m}^2\cdot\text{K}), while the outdoor air is at Tout=−10.0∘CT_{\text{out}} = -10.0^{\circ}\text{C} with an outdoor wind-induced convection coefficient hout=25.0 W/(m2⋅K)h_{\text{out}} = 25.0\text{ W}/(\text{m}^2\cdot\text{K}). Enforcing a coordinate direction xx pointing from the interior to the exterior, calculate: (a) the total thermal resistance RtotalR_{\text{total}} of the window system, (b) the signed rate of conductive-convective heat flow Q˙x\dot{Q}_x, and (c) the temperature of the innermost glass surface Ts,1T_{s,1}.

Answer and steps

Final answer

(a) Rtotal=0.358 K/WR_{\text{total}} = 0.358\text{ K}/\text{W}; (b) Q˙x=89.3 W\dot{Q}_x = 89.3\text{ W} (directed outdoors); (c) Ts,1=15.4∘CT_{s,1} = 15.4^{\circ}\text{C}.

Steps

01

Surface Area of the Window

The face area AA through which heat is transferred is: A=1.20 m×1.50 m=1.80 m2A = 1.20\text{ m} \times 1.50\text{ m} = 1.80\text{ m}^2


02

Part (a): Total Thermal Resistance RtotalR_{\text{total}}

The window unit behaves as a composite thermal wall with five thermal resistances connected in series along the heat flow path from the indoor air to the outdoor air:

  1. Interior Convective Boundary: Rconv,in=1hinA=17.50 W/(m2⋅K)×1.80 m2=113.5 K/W≈0.07407 K/WR_{\text{conv,in}} = \frac{1}{h_{\text{in}} A} = \frac{1}{7.50\text{ W}/(\text{m}^2\cdot\text{K}) \times 1.80\text{ m}^2} = \frac{1}{13.5}\text{ K/W} \approx 0.07407\text{ K/W}
  2. Inner Glass Pane (Conduction): Rg,1=LgkgA=4.00×10−3 m0.800 W/(m⋅K)×1.80 m2=0.004001.44 K/W≈0.00278 K/WR_{\text{g,1}} = \frac{L_g}{k_g A} = \frac{4.00 \times 10^{-3}\text{ m}}{0.800\text{ W}/(\text{m}\cdot\text{K}) \times 1.80\text{ m}^2} = \frac{0.00400}{1.44}\text{ K/W} \approx 0.00278\text{ K/W}
  3. Stagnant Air Gap (Conduction): Rair=LakaA=12.0×10−3 m0.0260 W/(m⋅K)×1.80 m2=0.01200.0468 K/W≈0.25641 K/WR_{\text{air}} = \frac{L_a}{k_a A} = \frac{12.0 \times 10^{-3}\text{ m}}{0.0260\text{ W}/(\text{m}\cdot\text{K}) \times 1.80\text{ m}^2} = \frac{0.0120}{0.0468}\text{ K/W} \approx 0.25641\text{ K/W}
  4. Outer Glass Pane (Conduction): Rg,2=Rg,1≈0.00278 K/WR_{\text{g,2}} = R_{\text{g,1}} \approx 0.00278\text{ K/W}
  5. Exterior Convective Boundary: Rconv,out=1houtA=125.0 W/(m2⋅K)×1.80 m2=145.0 K/W≈0.02222 K/WR_{\text{conv,out}} = \frac{1}{h_{\text{out}} A} = \frac{1}{25.0\text{ W}/(\text{m}^2\cdot\text{K}) \times 1.80\text{ m}^2} = \frac{1}{45.0}\text{ K/W} \approx 0.02222\text{ K/W}

Adding all resistances in series yields the total resistance: Rtotal=Rconv,in+Rg,1+Rair+Rg,2+Rconv,outR_{\text{total}} = R_{\text{conv,in}} + R_{\text{g,1}} + R_{\text{air}} + R_{\text{g,2}} + R_{\text{conv,out}} Rtotal=0.07407+0.00278+0.25641+0.00278+0.02222=0.35826 K/W≈0.358 K/WR_{\text{total}} = 0.07407 + 0.00278 + 0.25641 + 0.00278 + 0.02222 = 0.35826\text{ K/W} \approx 0.358\text{ K/W}


03

Part (b): Rate of Heat Flow Q˙x\dot{Q}_x

The temperature difference between the interior room air and the outdoor air is: ΔT=Tin−Tout=22.0∘C−(−10.0∘C)=32.0 K\Delta T = T_{\text{in}} - T_{\text{out}} = 22.0^{\circ}\text{C} - (-10.0^{\circ}\text{C}) = 32.0\text{ K}

Since the coordinate xx points from the warm interior toward the cold exterior, heat flows down the temperature gradient in the +x+x direction: Q˙x=ΔTRtotal=32.0 K0.35826 K/W≈89.3 W\dot{Q}_x = \frac{\Delta T}{R_{\text{total}}} = \frac{32.0\text{ K}}{0.35826\text{ K/W}} \approx 89.3\text{ W} The positive sign indicates heat is transferred from indoors to outdoors.


04

Part (c): Temperature of the Innermost Glass Surface Ts,1T_{s,1}

Across the interior boundary layer, heat is carried to the first glass surface via convection: Q˙x=Tin−Ts,1Rconv,in\dot{Q}_x = \frac{T_{\text{in}} - T_{s,1}}{R_{\text{conv,in}}}

Solving for the surface temperature Ts,1T_{s,1}: Ts,1=Tin−Q˙xRconv,inT_{s,1} = T_{\text{in}} - \dot{Q}_x R_{\text{conv,in}} Ts,1=22.0∘C−(89.32 W⋅0.07407 K/W)=22.0∘C−6.62∘C=15.38∘C≈15.4∘CT_{s,1} = 22.0^{\circ}\text{C} - (89.32\text{ W} \cdot 0.07407\text{ K/W}) = 22.0^{\circ}\text{C} - 6.62^{\circ}\text{C} = 15.38^{\circ}\text{C} \approx 15.4^{\circ}\text{C}

Typical errors

OverviewACEpath Teacher's Diagnosis

01 The student forgets to convert the millimetre layer thicknesses to metres when computing the conductive resistances, resulting in resistances three orders of magnitude too large.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Incorrect
  1. Step 1

    A=1.20×1.50=1.80 m2A = 1.20 \times 1.50 = 1.80\text{ m}^2 ⟹\Longrightarrow Rconv, in=17.50×1.80=0.0741 K/WR_{\text{conv, in}} = \frac{1}{7.50 \times 1.80} = 0.0741\text{ K/W} ⟹\Longrightarrow Rconv, out=125.0×1.80=0.0222 K/WR_{\text{conv, out}} = \frac{1}{25.0 \times 1.80} = 0.0222\text{ K/W}

  2. Step 2

    Rg=4.000.800×1.80=2.778 K/WR_g = \frac{4.00}{0.800 \times 1.80} = 2.778\text{ K/W} ⟹\Longrightarrow Rair=12.00.0260×1.80=256.41 K/WR_{\text{air}} = \frac{12.0}{0.0260 \times 1.80} = 256.41\text{ K/W}

    Correct

    Rg=4.00×10−3 m0.800 W/(m⋅K)×1.80 m2≈0.00278 K/WR_g = \frac{4.00 \times 10^{-3}\text{ m}}{0.800\text{ W}/(\text{m}\cdot\text{K}) \times 1.80\text{ m}^2} \approx 0.00278\text{ K/W} and Rair=12.0×10−3 m0.0260 W/(m⋅K)×1.80 m2≈0.2564 K/WR_{\text{air}} = \frac{12.0 \times 10^{-3}\text{ m}}{0.0260\text{ W}/(\text{m}\cdot\text{K}) \times 1.80\text{ m}^2} \approx 0.2564\text{ K/W}

    You used the layer thicknesses as 4.004.00 and 12.012.0 without converting millimeters to meters (1 mm=10−3 m1\text{ mm} = 10^{-3}\text{ m}), making both conductive resistances 10001000 times too large.

  3. Step 3

    Rtotal=0.0741+2×2.778+256.41+0.0222=262.06 K/WR_{\text{total}} = 0.0741 + 2 \times 2.778 + 256.41 + 0.0222 = 262.06\text{ K/W}

    Correct

    Rtotal=Rconv,in+2Rg+Rair+Rconv,out≈0.358 K/WR_{\text{total}} = R_{\text{conv,in}} + 2R_g + R_{\text{air}} + R_{\text{conv,out}} \approx 0.358\text{ K/W}

    Your formula correctly summed the five series resistances, but the value was inflated by the unconverted conduction resistances.

  4. Step 4

    Q˙x=22.0−(−10.0)262.06⟹Q˙x=32.0262.06=0.122 W\dot{Q}_x = \frac{22.0 - (-10.0)}{262.06} \Longrightarrow \dot{Q}_x = \frac{32.0}{262.06} = 0.122\text{ W}

    Correct

    Q˙x=ΔTRtotal=32.0 K0.35826 K/W≈89.3 W\dot{Q}_x = \frac{\Delta T}{R_{\text{total}}} = \frac{32.0\text{ K}}{0.35826\text{ K/W}} \approx 89.3\text{ W}

    You applied Fourier's rate equation correctly using the full temperature difference, but the inflated resistance resulted in an artificially small heat flow.

  5. Step 5

    Tin−Ts,1=Q˙x×Rconv, in⟹Ts,1=22.0−0.122×0.0741=21.99∘CT_{\text{in}} - T_{s,1} = \dot{Q}_x \times R_{\text{conv, in}} \Longrightarrow T_{s,1} = 22.0 - 0.122 \times 0.0741 = 21.99^{\circ}\text{C}

    Correct

    Ts,1=Tin−Q˙xRconv,in=22.0∘C−(89.32 W)(0.07407 K/W)≈15.4∘CT_{s,1} = T_{\text{in}} - \dot{Q}_x R_{\text{conv,in}} = 22.0^{\circ}\text{C} - (89.32\text{ W})(0.07407\text{ K/W}) \approx 15.4^{\circ}\text{C}

    Your temperature-drop relation across the indoor boundary layer was set up correctly, but substituting the incorrect heat flow caused Ts,1T_{s,1} to barely drop below the indoor room temperature.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly identified the composite structure as a 5-layer series thermal network.

You used the correct expressions for convective thermal resistance R=1hAR = \frac{1}{hA} and conductive thermal resistance R=LkAR = \frac{L}{kA}.

You correctly related the local temperature drop across the inner surface layer to the total heat transfer rate.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Unit conversion omission (mm to m)

You substituted the layer thicknesses Lg=4.00L_g = 4.00 and La=12.0L_a = 12.0 directly in millimeters instead of converting them to meters.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Overlooking the SI base unit requirement for length in the thermal conductivity definition (kk in W/(m⋅K)\text{W}/(\text{m}\cdot\text{K})). When kk uses meters, thickness LL must also be in meters so the length units cancel properly.

REASONING PATH
Your ACEpath teacher’s suggested approach
Check SI Unit Homogeneity
  • Thermal conductivity is given in W/(m⋅K)\text{W}/(\text{m}\cdot\text{K}), while area is in m2\text{m}^2. Therefore, length LL in R=LkAR = \frac{L}{kA} must be expressed in meters (m\text{m}).

  • Multiply millimeter dimensions by 10−3 m/mm10^{-3}\text{ m/mm} before substituting into resistance formulas.

Physical Reality Check on Window Heat Loss
  • A typical double-pane window of area ≈1.8 m2\approx 1.8\text{ m}^2 under a 32∘C32^{\circ}\text{C} temperature differential loses roughly 50 W50\text{ W} to 150 W150\text{ W}, not a fraction of a watt.

  • If your calculated heat flow is under 1 W1\text{ W} for an entire exterior window in winter, check whether your conduction resistances were accidentally scaled by 10310^3.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Convert thicknesses to meters: Lg=4.00×10−3 mL_g = 4.00 \times 10^{-3}\text{ m} and La=12.0×10−3 mL_a = 12.0 \times 10^{-3}\text{ m}.

  2. Compute the correct conductive resistances: Rg=4.00×10−30.800×1.80≈0.00278 K/WR_g = \frac{4.00 \times 10^{-3}}{0.800 \times 1.80} \approx 0.00278\text{ K/W} and Rair=12.0×10−30.0260×1.80≈0.25641 K/WR_{\text{air}} = \frac{12.0 \times 10^{-3}}{0.0260 \times 1.80} \approx 0.25641\text{ K/W}.

  3. Sum all five series resistances: Rtotal=0.07407+2(0.00278)+0.25641+0.02222=0.35826 K/W≈0.358 K/WR_{\text{total}} = 0.07407 + 2(0.00278) + 0.25641 + 0.02222 = 0.35826\text{ K/W} \approx 0.358\text{ K/W}.

  4. Compute the overall heat flow: Q˙x=22.0−(−10.0)0.35826=32.00.35826≈89.3 W\dot{Q}_x = \frac{22.0 - (-10.0)}{0.35826} = \frac{32.0}{0.35826} \approx 89.3\text{ W}.

  5. Compute the surface temperature: Ts,1=22.0−(89.32)(0.07407)=22.0−6.62=15.38∘C≈15.4∘CT_{s,1} = 22.0 - (89.32)(0.07407) = 22.0 - 6.62 = 15.38^{\circ}\text{C} \approx 15.4^{\circ}\text{C}.

Final answer

(a) Rtotal=0.358 K/WR_{\text{total}} = 0.358\text{ K/W}; (b) Q˙x=89.3 W\dot{Q}_x = 89.3\text{ W}; (c) Ts,1=15.4∘CT_{s,1} = 15.4^{\circ}\text{C}

NEXT STEPS
Final Takeaways from Your Teacher
  • Always write down the explicit unit next to each variable before plugging into a formula (e.g., L=4.00 mm=4.00×10−3 mL = 4.00\text{ mm} = 4.00 \times 10^{-3}\text{ m}).

  • Perform dimensional analysis on R=LkAR = \frac{L}{kA}: m[W/(m⋅K)](m2)=mW⋅m/K=K/W\frac{\text{m}}{[\text{W}/(\text{m}\cdot\text{K})](\text{m}^2)} = \frac{\text{m}}{\text{W}\cdot\text{m}/\text{K}} = \text{K/W}. If you substitute millimeters without conversion, you get 1000 K/W1000\text{ K/W}.

  • Practice using thermal resistance networks on composite walls with varying unit prefixes (cm, mm, inches).

OverviewACEpath Teacher's Diagnosis

02 The student calculates unit-area thermal resistances instead of total thermal resistance by omitting the surface area A from all resistance formulas.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Rconv,in=17.50=0.1333 K/W  ⟹  Rg1=Rg2=0.004000.800=0.00500 K/W  ⟹  Rair=0.01200.0260=0.4615 K/W  ⟹  Rconv,out=125.0=0.0400 K/W  ⟹  Rtotal=0.1333+0.00500+0.4615+0.00500+0.0400=0.6448 K/WR_{\text{conv,in}} = \frac{1}{7.50} = 0.1333\text{ K/W} \implies R_{g1} = R_{g2} = \frac{0.00400}{0.800} = 0.00500\text{ K/W} \implies R_{\text{air}} = \frac{0.0120}{0.0260} = 0.4615\text{ K/W} \implies R_{\text{conv,out}} = \frac{1}{25.0} = 0.0400\text{ K/W} \implies R_{\text{total}} = 0.1333 + 0.00500 + 0.4615 + 0.00500 + 0.0400 = 0.6448\text{ K/W}

    Correct

    A=1.20 m×1.50 m=1.80 m2  ⟹  Rtotal=1hinA+2(LgkgA)+LakaA+1houtA=0.6448 m2⋅K/W1.80 m2≈0.358 K/WA = 1.20\text{ m} \times 1.50\text{ m} = 1.80\text{ m}^2 \implies R_{\text{total}} = \frac{1}{h_{\text{in}}A} + 2\left(\frac{L_g}{k_g A}\right) + \frac{L_a}{k_a A} + \frac{1}{h_{\text{out}}A} = \frac{0.6448\text{ m}^2\cdot\text{K/W}}{1.80\text{ m}^2} \approx 0.358\text{ K/W}

    You calculated the unit-area thermal resistances R′′=1hR'' = \frac{1}{h} and R′′=LkR'' = \frac{L}{k} instead of the total resistances R=1hAR = \frac{1}{hA} and R=LkAR = \frac{L}{kA}. Because you omitted the window face area A=1.80 m2A = 1.80\text{ m}^2, your total resistance was a factor of 1.801.80 too high.

  2. Step 2

    Q˙x=22.0−(−10.0)0.6448  ⟹  Q˙x=32.00.6448=49.63 W\dot{Q}_x = \frac{22.0 - (-10.0)}{0.6448} \implies \dot{Q}_x = \frac{32.0}{0.6448} = 49.63\text{ W}

    Correct

    Q˙x=ΔTRtotal=32.0 K0.35826 K/W≈89.3 W\dot{Q}_x = \frac{\Delta T}{R_{\text{total}}} = \frac{32.0\text{ K}}{0.35826\text{ K/W}} \approx 89.3\text{ W}

    You correctly applied the driving temperature difference across the composite resistance, but your numerical value represents the heat flux q′′=49.63 W/m2q'' = 49.63\text{ W/m}^2 because it carried forward the unit-area resistance from step 1.

  3. Step 3

    Ts,1=22.0−49.63×0.1333  ⟹  Ts,1=22.0−6.62=15.38∘CT_{s,1} = 22.0 - 49.63 \times 0.1333 \implies T_{s,1} = 22.0 - 6.62 = 15.38^{\circ}\text{C}

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly identified that the five thermal layers act in series.

You correctly identified the temperature difference ΔT=32.0 K\Delta T = 32.0\text{ K} along the coordinate direction xx.

You applied the thermal Ohm's law and boundary temperature drop formulas correctly.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Omission of Surface Area in Thermal Resistance

You evaluated unit-area thermal resistances R′′R'' (in m2⋅K/W\text{m}^2\cdot\text{K}/\text{W}) but labeled them with total resistance units K/W\text{K}/\text{W}.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Conflating absolute thermal resistance RR (units of K/W\text{K}/\text{W}) with unit-area (specific) thermal resistance R′′R'' (units of m2⋅K/W\text{m}^2\cdot\text{K}/\text{W}). When calculating total heat flow rate Q˙\dot{Q} in Watts, the face area AA must appear in the denominator of every conduction (L/(kA)L/(kA)) and convection (1/(hA)1/(hA)) resistance.

REASONING PATH
Your ACEpath teacher’s suggested approach
Check Units on Thermal Resistance
  • Total thermal resistance has units of K/W\text{K}/\text{W} and includes cross-sectional area AA: Rcond=LkAR_{\text{cond}} = \frac{L}{kA} and Rconv=1hAR_{\text{conv}} = \frac{1}{hA}.

  • Always verify that the units of 1/h1/h are m2⋅K/W\text{m}^2\cdot\text{K}/\text{W}. Divide by AA in m2\text{m}^2 to convert to K/W\text{K}/\text{W}.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Calculate the face area of the window: A=1.20 m×1.50 m=1.80 m2A = 1.20\text{ m} \times 1.50\text{ m} = 1.80\text{ m}^2.

  2. Divide the unit-area thermal resistance by the face area to get the absolute thermal resistance: Rtotal=Rtotal′′A=0.6448 m2⋅K/W1.80 m2≈0.358 K/WR_{\text{total}} = \frac{R''_{\text{total}}}{A} = \frac{0.6448\text{ m}^2\cdot\text{K/W}}{1.80\text{ m}^2} \approx 0.358\text{ K/W}.

  3. Compute the total heat flow rate: Q˙x=ΔTRtotal=32.0 K0.35826 K/W≈89.3 W\dot{Q}_x = \frac{\Delta T}{R_{\text{total}}} = \frac{32.0\text{ K}}{0.35826\text{ K/W}} \approx 89.3\text{ W}.

Final answer

(a) Rtotal=0.358 K/WR_{\text{total}} = 0.358\text{ K}/\text{W}; (b) Q˙x=89.3 W\dot{Q}_x = 89.3\text{ W}; (c) Ts,1=15.4∘CT_{s,1} = 15.4^{\circ}\text{C}

NEXT STEPS
Final Takeaways from Your Teacher
  • Before substituting numbers into R=L/kR = L/k or R=1/hR = 1/h, check whether you need heat flux q′′q'' (W/m²) or total heat transfer rate Q˙\dot{Q} (W).

  • Carry units through intermediate calculations to catch missing area terms immediately.

OverviewACEpath Teacher's Diagnosis

03 The student accounts for only one glass pane instead of two in the series resistance network.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Incorrect
  1. Step 1

    A = 1.20 ×\times 1.50 = 1.80 m\text{ m}^2   ⟹  \implies R_{conv,in\text{conv,in}} = 17.50×1.80\frac{1}{7.50 \times 1.80} = 0.0741 K/W\text{ K/W}   ⟹  \implies R_g = 0.004000.800×1.80\frac{0.00400}{0.800 \times 1.80} = 0.0028 K/W\text{ K/W}   ⟹  \implies R_{air\text{air}} = 0.01200.0260×1.80\frac{0.0120}{0.0260 \times 1.80} = 0.2564 K/W\text{ K/W}   ⟹  \implies R_{conv,out\text{conv,out}} = 125.0×1.80\frac{1}{25.0 \times 1.80} = 0.0222 K/W\text{ K/W}_

  2. Step 2

    R_{total\text{total}} = 0.0741 + 0.0028 + 0.2564 + 0.0222 = 0.3555 K/W\text{ K/W}_

    Correct

    R_{total\text{total}} = R_{conv,in\text{conv,in}} + R_{g,1} + R_{air\text{air}} + R_{g,2} + R_{conv,out\text{conv,out}} = 0.07407 + 0.00278 + 0.25641 + 0.00278 + 0.02222 ≈\approx 0.358 K/W\text{ K/W}

    A double-pane window consists of two separate glass panes enclosing an air layer. Your summation only included one glass layer (RgR_g), omitting the outer pane (Rg,2R_{g,2}).

  3. Step 3

    \dot{Q}x = 22.0−(−10.0)0.3555\frac{22.0 - (-10.0)}{0.3555} = 32.00.3555\frac{32.0}{0.3555} = 90.01 W\text{ W}

    Correct

    \dot{Q}x = ΔTRtotal\frac{\Delta T}{R_{\text{total}}} = 32.0 K0.35826 K/W\frac{32.0\text{ K}}{0.35826\text{ K/W}} ≈\approx 89.3 W\text{ W}

    Your setup using Q˙x=ΔTRtotal\dot{Q}_x = \frac{\Delta T}{R_{\text{total}}} is conceptually sound, but the numerical result is affected by the missing glass resistance in RtotalR_{\text{total}}.

  4. Step 4

    T_{s,1} = 22.0 - 90.01 ×\times 0.0741 = 22.0 - 6.67 = 15.33^{∘\circ}C\text{C}_

    Correct

    T_{s,1} = T_{in\text{in}} - \dot{Q}x R{conv,in\text{conv,in}} = 22.0^{∘\circ}C\text{C} - (89.32 W\text{ W})(0.07407 K/W\text{ K/W}) ≈\approx 15.4^{∘\circ}C\text{C}

    Your relationship for the inner surface temperature across the interior convective boundary layer is correct, but your value is slightly off due to the propagated heat rate Q˙x\dot{Q}_x.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly calculated the window area as 1.80 m21.80\text{ m}^2.

You used the correct resistance formulas for both convection, R=1hAR = \frac{1}{hA}, and conduction, R=LkAR = \frac{L}{kA}.

You correctly related the inner surface temperature to the indoor air temperature and convective heat transfer.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Omitted component in series network

You calculated the thermal resistance of one glass pane (0.0028 K/W0.0028\text{ K/W}) but only added it once to your total series sum.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Overlooking that a double-pane insulating glass unit contains two separate physical solid boundaries (an inner pane and an outer pane) that both contribute conduction resistance to the series thermal circuit.

REASONING PATH
Your ACEpath teacher’s suggested approach
Count all physical layers
  • Every solid layer and fluid boundary along the 1D path adds a resistance in series: NN solid sheets plus MM fluid gaps plus 2 convective boundary layers.

  • Sketch the cross section and write down a labeled node for each boundary to ensure every layer is represented in the resistance sum.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Include both glass panes in the series network: Rtotal=Rconv,in+Rg,1+Rair+Rg,2+Rconv,outR_{\text{total}} = R_{\text{conv,in}} + R_{g,1} + R_{\text{air}} + R_{g,2} + R_{\text{conv,out}}.

  2. Sum the values: Rtotal=0.07407+0.00278+0.25641+0.00278+0.02222=0.35826 K/W≈0.358 K/WR_{\text{total}} = 0.07407 + 0.00278 + 0.25641 + 0.00278 + 0.02222 = 0.35826\text{ K/W} \approx 0.358\text{ K/W}.

  3. Recalculate heat rate: Q˙x=32.0 K0.35826 K/W=89.32 W\dot{Q}_x = \frac{32.0\text{ K}}{0.35826\text{ K/W}} = 89.32\text{ W}.

  4. Recalculate inner surface temperature: Ts,1=22.0∘C−(89.32 W)(0.07407 K/W)=15.38∘C≈15.4∘CT_{s,1} = 22.0^{\circ}\text{C} - (89.32\text{ W})(0.07407\text{ K/W}) = 15.38^{\circ}\text{C} \approx 15.4^{\circ}\text{C}.

Final answer

(a) Rtotal=0.358 K/WR_{\text{total}} = 0.358\text{ K/W}, (b) Q˙x=89.3 W\dot{Q}_x = 89.3\text{ W}, (c) Ts,1=15.4∘CT_{s,1} = 15.4^{\circ}\text{C}

NEXT STEPS
Final Takeaways from Your Teacher
  • Draw an equivalent thermal circuit diagram before writing numbers so you can count nodes and resistors.

  • Verify that a double-pane window has 5 thermal resistances in series: 2 convection films + 2 glass panes + 1 air gap.

  • Practice composite wall problems with multiple identical layers to avoid omitting symmetric elements.

Lock it in

Similar question

01

A single pane of glass has thickness L=6.00 mmL = 6.00\text{ mm}, area A=2.00 m2A = 2.00\text{ m}^2, and thermal conductivity k=0.750 W/(m⋅K)k = 0.750\text{ W}/(\text{m}\cdot\text{K}). Convective heat transfer coefficients are hin=8.00 W/(m2⋅K)h_{\text{in}} = 8.00\text{ W}/(\text{m}^2\cdot\text{K}) on the inside and hout=20.0 W/(m2⋅K)h_{\text{out}} = 20.0\text{ W}/(\text{m}^2\cdot\text{K}) on the outside. Calculate the total thermal resistance RtotalR_{\text{total}} of the single-pane system.

Answer

Rtotal=0.0915 K/WR_{\text{total}} = 0.0915\text{ K/W}. Steps: L=6.00×10−3 mL = 6.00 \times 10^{-3}\text{ m}; Rconv,in=18.00×2.00=0.0625 K/WR_{\text{conv,in}} = \frac{1}{8.00 \times 2.00} = 0.0625\text{ K/W}; Rglass=0.006000.750×2.00=0.00400 K/WR_{\text{glass}} = \frac{0.00600}{0.750 \times 2.00} = 0.00400\text{ K/W}; Rconv,out=120.0×2.00=0.0250 K/WR_{\text{conv,out}} = \frac{1}{20.0 \times 2.00} = 0.0250\text{ K/W}; Rtotal=0.0625+0.0040+0.0250=0.0915 K/WR_{\text{total}} = 0.0625 + 0.0040 + 0.0250 = 0.0915\text{ K/W}.

02

An insulated wall of area A=10.0 m2A = 10.0\text{ m}^2 consists of a 15.0 mm15.0\text{ mm} layer of plaster (k=0.300 W/(m⋅K)k = 0.300\text{ W}/(\text{m}\cdot\text{K})) and a 50.0 mm50.0\text{ mm} layer of fiberglass insulation (k=0.0400 W/(m⋅K)k = 0.0400\text{ W}/(\text{m}\cdot\text{K})). Neglecting surface convection, find the rate of heat conduction Q˙\dot{Q} when the inner surface is at 20.0∘C20.0^{\circ}\text{C} and the outer surface is at −5.00∘C-5.00^{\circ}\text{C}.

Answer

Q˙=192 W\dot{Q} = 192\text{ W}. Steps: L1=0.0150 m  ⟹  R1=0.01500.300×10.0=0.00500 K/WL_1 = 0.0150\text{ m} \implies R_1 = \frac{0.0150}{0.300 \times 10.0} = 0.00500\text{ K/W}; L2=0.0500 m  ⟹  R2=0.05000.0400×10.0=0.1250 K/WL_2 = 0.0500\text{ m} \implies R_2 = \frac{0.0500}{0.0400 \times 10.0} = 0.1250\text{ K/W}; Rtotal=0.1300 K/WR_{\text{total}} = 0.1300\text{ K/W}; Q˙=20.0−(−5.00)0.1300=25.00.1300≈192.3 W\dot{Q} = \frac{20.0 - (-5.00)}{0.1300} = \frac{25.0}{0.1300} \approx 192.3\text{ W}.

03

A triple-pane window consists of three identical glass panes (Lg=3.00 mmL_g = 3.00\text{ mm}, kg=0.900 W/(m⋅K)k_g = 0.900\text{ W}/(\text{m}\cdot\text{K})) separated by two identical argon gas gaps (Lar=10.0 mmL_{\text{ar}} = 10.0\text{ mm}, kar=0.0160 W/(m⋅K)k_{\text{ar}} = 0.0160\text{ W}/(\text{m}\cdot\text{K})). For a window of area A=1.50 m2A = 1.50\text{ m}^2 with inner convection coefficient hin=8.00 W/(m2⋅K)h_{\text{in}} = 8.00\text{ W}/(\text{m}^2\cdot\text{K}) and outer convection coefficient hout=24.0 W/(m2⋅K)h_{\text{out}} = 24.0\text{ W}/(\text{m}^2\cdot\text{K}), find the overall heat transfer rate Q˙\dot{Q} when Tin=21.0∘CT_{\text{in}} = 21.0^{\circ}\text{C} and Tout=−15.0∘CT_{\text{out}} = -15.0^{\circ}\text{C}.

Answer

Q˙=37.8 W\dot{Q} = 37.8\text{ W}. Steps: Rconv,in=18×1.5≈0.08333 K/WR_{\text{conv,in}} = \frac{1}{8 \times 1.5} \approx 0.08333\text{ K/W}; 3Rg=3×0.0030.9×1.5=0.00667 K/W3 R_g = 3 \times \frac{0.003}{0.9 \times 1.5} = 0.00667\text{ K/W}; 2Rar=2×0.0100.016×1.5≈0.83333 K/W2 R_{\text{ar}} = 2 \times \frac{0.010}{0.016 \times 1.5} \approx 0.83333\text{ K/W}; Rconv,out=124×1.5≈0.02778 K/WR_{\text{conv,out}} = \frac{1}{24 \times 1.5} \approx 0.02778\text{ K/W}; Rtotal≈0.9511 K/WR_{\text{total}} \approx 0.9511\text{ K/W}; Q˙=21.0−(−15.0)0.9511=36.00.9511≈37.8 W\dot{Q} = \frac{21.0 - (-15.0)}{0.9511} = \frac{36.0}{0.9511} \approx 37.8\text{ W}.

Loading workspace…