A student computes the electrical power dissipated by an industrial transmission line of total resistance R=4.00 ΩR = 4.00\,\Omega carrying an alternating current of root-mean-square magnitude Irms=250 AI_{\text{rms}} = 250\text{ A}. Confusing the voltage drop across the line with the line-to-neutral system voltage Vline=120 kVV_{\text{line}} = 120\text{ kV}, the student calculates power via P=Vline2R=(1.20×105)24.00=3.60×109 WP = \frac{V_{\text{line}}^2}{R} = \frac{(1.20 \times 10^5)^2}{4.00} = 3.60 \times 10^9\text{ W}. (a) Carry out an order-of-magnitude and sanity check to explain why 3.60 GW3.60\text{ GW} is physically absurd for line dissipation. (b) Compute the correct power loss using Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R and verify that its units reduce to W\text{W} (J/s\text{J}/\text{s}).

Answer and steps

Final answer

(a) A transmission dissipation of 3.60 GW3.60\text{ GW} exceeds the total generation capacity of typical large commercial power stations (1 to 2 GW1\text{ to }2\text{ GW}), indicating that using overall grid voltage rather than the line voltage drop ΔV=IR\Delta V = I R leads to an absurd overestimation by six orders of magnitude; (b) Pdiss=2.50×105 W=250 kWP_{\text{diss}} = 2.50 \times 10^5\text{ W} = 250\text{ kW}.

Steps

Part (a): Order-of-Magnitude and Sanity Check

  1. Physical Meaning of the System Voltage vs. Line Drop: The value Vline=120 kVV_{\text{line}} = 120\text{ kV} is the electric potential of the line relative to ground (or neutral), which drives current to consumers across the entire electrical grid. In contrast, the voltage relevant to power dissipated inside the wire is the potential drop across the wire itself: ΔVwire=IrmsR=(250 A)(4.00 Ω)=1.00×103 V=1.00 kV\Delta V_{\text{wire}} = I_{\text{rms}} R = (250\text{ A})(4.00\,\Omega) = 1.00 \times 10^3\text{ V} = 1.00\text{ kV}
  2. Sanity Check against Real-World Scales:

    • A typical large commercial power plant (such as a modern nuclear or coal facility) generates between 1 GW1\text{ GW} and 2 GW2\text{ GW} of total electrical power.
    • A line dissipation of 3.60 GW3.60\text{ GW} (3.60×109 W3.60 \times 10^9\text{ W}) would mean that more energy than the entire output of two large power plants is converted directly into waste heat along a single transmission line.
    • The total power transmitted through the line is on the order of: Ptransmitted≈VlineIrms=(1.20×105 V)(250 A)=3.00×107 W=30.0 MWP_{\text{transmitted}} \approx V_{\text{line}} I_{\text{rms}} = (1.20 \times 10^5\text{ V})(250\text{ A}) = 3.00 \times 10^7\text{ W} = 30.0\text{ MW} The student's calculated loss (3600 MW3600\text{ MW}) exceeds the total transmitted power by a factor of over 100100, which violates energy conservation. Thus, an answer of 3.60 GW3.60\text{ GW} is physically impossible.

Part (b): Correct Calculation and Unit Verification

  1. Calculating Correct Power Dissipation: Using Joule's law with the actual current flowing through the line resistance: Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R Substitute the given values: Pdiss=(250 A)2⋅(4.00 Ω)=(6.25×104 A2)(4.00 Ω)=2.50×105 W=250 kWP_{\text{diss}} = (250\text{ A})^2 \cdot (4.00\,\Omega) = (6.25 \times 10^4\text{ A}^2)(4.00\,\Omega) = 2.50 \times 10^5\text{ W} = 250\text{ kW}
  2. Unit Verification:

    • From Ohm's law, resistance is electric potential divided by current: 1 Ω=1 VA1\,\Omega = 1\,\frac{\text{V}}{\text{A}}
    • Therefore, the units of I2RI^2 R are: [A2⋅Ω]=A2⋅VA=A⋅V[\text{A}^2 \cdot \Omega] = \text{A}^2 \cdot \frac{\text{V}}{\text{A}} = \text{A} \cdot \text{V}
    • Electric potential is energy per unit charge (V=J/C\text{V} = \text{J}/\text{C}), and current is charge per unit time (A=C/s\text{A} = \text{C}/\text{s}): A⋅V=(Cs)⋅(JC)=Js=W\text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right) \cdot \left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W} The units consistently reduce to watts (W\text{W}), confirming that Pdiss=2.50×105 W=250 kWP_{\text{diss}} = 2.50 \times 10^5\text{ W} = 250\text{ kW}.

Typical errors

OverviewACEpath Teacher's Diagnosis

01 The student forgets to square the current when calculating dissipated power using P = I²R, resulting in an understated power loss of 1000 W.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    3.60 GW3.60\text{ GW} is larger than the output of an entire commercial power plant, which would melt the transmission line instantly.

  2. Step 2

    Pdiss=IrmsR=(250 A)(4.00 Ω)=1000 WP_{\text{diss}} = I_{\text{rms}} R = (250\text{ A})(4.00\,\Omega) = 1000\text{ W}

    Correct

    Pdiss=Irms2R=(250 A)2(4.00 Ω)=2.50×105 W=250 kWP_{\text{diss}} = I_{\text{rms}}^2 R = (250\text{ A})^2(4.00\,\Omega) = 2.50 \times 10^5\text{ W} = 250\text{ kW}

    You omitted the exponent 22 on the current. The expression IRI R yields the voltage drop ΔV\Delta V across the line in volts, whereas Joule heating requires I2RI^2 R.

  3. Step 3

    Units: A Ω=V=J/C≠W, so unit check fails\text{Units: } \text{A}\,\Omega = \text{V} = \text{J}/\text{C} \neq \text{W}\text{, so unit check fails}

    Correct

    [I2R]=A2⋅Ω=A2⋅(VA)=A⋅V=(Cs)(JC)=Js=W[I^2 R] = \text{A}^2 \cdot \Omega = \text{A}^2 \cdot \left(\frac{\text{V}}{\text{A}}\right) = \text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right)\left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W}

    Your unit reduction for your written formula A Ω\text{A}\,\Omega was mathematically sound, but because the square on current was missing, you evaluated IRI R instead of I2RI^2 R.

WHAT YOU DID WELL
Compliments from Your Teacher

You provided a clear, accurate order-of-magnitude comparison between 3.60 GW3.60\text{ GW} and commercial power plant capacities.

You correctly tested the dimensional consistency of your expression and properly concluded that A Ω=V=J/C\text{A}\,\Omega = \text{V} = \text{J}/\text{C} does not equal watts.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Omitted Exponent in Formula

You wrote Pdiss=IrmsRP_{\text{diss}} = I_{\text{rms}} R instead of Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R, confusing electrical power dissipation with potential drop ΔV\Delta V.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Conflating Ohm's law for potential difference (ΔV=IR\Delta V = I R, with units of volts) with Joule's law for thermal power dissipation (P=I2RP = I^2 R, with units of watts). When your unit check revealed volts rather than watts, you concluded that the check failed rather than using that dimensional mismatch to correct the missing factor of current.

REASONING PATH
Your ACEpath teacher’s suggested approach
Formula Differentiation
  • ΔV=IR\Delta V = I R measures electric potential difference in volts (V\text{V}); P=IΔV=I2R=ΔV2RP = I \Delta V = I^2 R = \frac{\Delta V^2}{R} measures energy dissipation rate in watts (W\text{W}).

  • Always verify whether you are solving for potential drop across a component or power dissipated within it before writing down the relationship.

Using Dimensional Checks to Fix Missing Factors
  • If your unit analysis results in V\text{V} (J/C\text{J}/\text{C}) instead of W\text{W} (J/s\text{J}/\text{s}), the expression lacks a factor with units of A=C/s\text{A} = \text{C}/\text{s} because V⋅A=W\text{V} \cdot \text{A} = \text{W}.

  • When a unit check fails by a factor of current, multiply by another factor of II to see if an exponent was omitted.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Write down Joule's dissipation law with the squared current: Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R.

  2. Substitute Irms=250 AI_{\text{rms}} = 250\text{ A} and R=4.00 ΩR = 4.00\,\Omega: Pdiss=(250 A)2⋅4.00 Ω=62 500 A2⋅4.00 ΩP_{\text{diss}} = (250\text{ A})^2 \cdot 4.00\,\Omega = 62\,500\text{ A}^2 \cdot 4.00\,\Omega.

  3. Multiply to evaluate: Pdiss=250 000 W=250 kWP_{\text{diss}} = 250\,000\text{ W} = 250\text{ kW}.

  4. Perform the dimensional check on I2RI^2 R: A2⋅Ω=A⋅(A⋅Ω)=A⋅V=(Cs)(JC)=Js=W\text{A}^2 \cdot \Omega = \text{A} \cdot (\text{A} \cdot \Omega) = \text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right)\left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W}.

Final answer

(a) 3.60 GW3.60\text{ GW} exceeds the output of typical large power plants (1 to 2 GW1\text{ to }2\text{ GW}); (b) Pdiss=2.50×105 W=250 kWP_{\text{diss}} = 2.50 \times 10^5\text{ W} = 250\text{ kW}, with units A2⋅Ω=W\text{A}^2 \cdot \Omega = \text{W}.

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the distinct physical roles and SI units of voltage drop ΔV=IR\Delta V = I R versus dissipated power P=I2RP = I^2 R.

  • Practice using unit analysis as an active diagnostic tool to identify missing algebraic terms whenever dimensions do not balance.

OverviewACEpath Teacher's Diagnosis

02 The student confuses the line resistance with line current and calculates power using V_line × I_rms, finding the total apparent power delivered instead of the line dissipation.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    3.60 GW exceeds the total generating capacity of several nuclear reactors, meaning the wires would instantly vaporize from heat.

  2. Step 2

    Pdiss=VlineIrms=(120000 V)(250 A)=30000000 W=3.00×107 WP_{\text{diss}} = V_{\text{line}} I_{\text{rms}} = (120000\text{ V})(250\text{ A}) = 30000000\text{ W} = 3.00 \times 10^7\text{ W}

    Correct

    Pdiss=Irms2R=(250 A)2(4.00 Ω)=2.50×105 W=250 kWP_{\text{diss}} = I_{\text{rms}}^2 R = (250\text{ A})^2 (4.00\,\Omega) = 2.50 \times 10^5\text{ W} = 250\text{ kW}

    You calculated the total transmitted power P=VlineIrmsP = V_{\text{line}} I_{\text{rms}} (30 MW30\text{ MW}) rather than the thermal power dissipated along the wire Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R (250 kW250\text{ kW}).

  3. Step 3

    Units: V A=(J/C)(C/s)=J/s=W\text{Units: } \text{V } \text{A} = (\text{J}/\text{C})(\text{C}/\text{s}) = \text{J}/\text{s} = \text{W}

    Correct

    [I2R]=A2⋅Ω=A2⋅(VA)=A⋅V=(Cs)(JC)=Js=W[I^2 R] = \text{A}^2 \cdot \Omega = \text{A}^2 \cdot \left(\frac{\text{V}}{\text{A}}\right) = \text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right)\left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W}

    Because you used P=VIP = V I, your unit verification started directly with V⋅A\text{V} \cdot \text{A} rather than reducing A2⋅Ω\text{A}^2 \cdot \Omega to watts.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly recognized that 3.60 GW3.60\text{ GW} is an absurdly large power loss compared to power plant generation capacities.

You accurately showed that the product of volts and amperes reduces to joules per second (watts).

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Confusing Transmitted Power with Line Dissipation

You used the total transmission line voltage VlineV_{\text{line}} in VIV I instead of calculating the resistive loss across the wire using Irms2RI_{\text{rms}}^2 R.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You conflated system potential relative to ground (VlineV_{\text{line}}), which determines total delivered power, with the voltage drop along the conductor (ΔV=IR\Delta V = I R), which determines thermal power loss.

REASONING PATH
Your ACEpath teacher’s suggested approach
System Voltage vs. Line Voltage Drop
  • The potential to ground VlineV_{\text{line}} governs transmitted power (Ptrans≈VlineIP_{\text{trans}} \approx V_{\text{line}} I), whereas only the potential drop across the wire itself (ΔVwire=IR\Delta V_{\text{wire}} = I R) causes resistive heat dissipation.

  • Whenever finding wire losses, compute directly via Pdiss=I2RP_{\text{diss}} = I^2 R or (ΔVwire)2R\frac{(\Delta V_{\text{wire}})^2}{R}, never with VlineV_{\text{line}}.

Unit Chain for Ohmic Dissipation
  • [Ω]=VA[\Omega] = \frac{\text{V}}{\text{A}}, so [I2R]=A2⋅VA=A⋅V=W[I^2 R] = \text{A}^2 \cdot \frac{\text{V}}{\text{A}} = \text{A} \cdot \text{V} = \text{W}.

  • Show the substitution of 1 Ω=1 V/A1\,\Omega = 1\,\text{V}/\text{A} before converting electrical units to mechanical energy rates.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Substitute the line current and resistance into Joule's dissipation formula: Pdiss=Irms2R=(250 A)2⋅(4.00 Ω)P_{\text{diss}} = I_{\text{rms}}^2 R = (250\text{ A})^2 \cdot (4.00\,\Omega).

  2. Calculate the numerical power loss: Pdiss=(6.25×104 A2)(4.00 Ω)=2.50×105 W=250 kWP_{\text{diss}} = (6.25 \times 10^4\text{ A}^2)(4.00\,\Omega) = 2.50 \times 10^5\text{ W} = 250\text{ kW}.

  3. Verify units from first principles: [I2R]=A2⋅Ω=A2(VA)=A⋅V=(Cs)(JC)=Js=W[I^2 R] = \text{A}^2 \cdot \Omega = \text{A}^2 \left(\frac{\text{V}}{\text{A}}\right) = \text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right)\left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W}.

Final answer

Pdiss=2.50×105 W=250 kWP_{\text{diss}} = 2.50 \times 10^5\text{ W} = 250\text{ kW}

NEXT STEPS
Final Takeaways from Your Teacher
  • Practice distinguishing between total load power (VsourceIV_{\text{source}} I) and parasitic wire loss (I2RwireI^2 R_{\text{wire}}).

  • Review dimensional reduction of derived electrical units starting from resistance (Ω=V/A\Omega = \text{V}/\text{A}).

  • Solve the three targeted follow-up practice exercises below to solidify when to apply I2RI^2 R versus VIV I.

OverviewACEpath Teacher's Diagnosis

03 The student calculates the line voltage drop V_drop = I_rms R = 1000 V correctly but squares the resistance instead of current, computing P = I R² = 4000 W.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    3.60 GW is absurd because a typical nuclear plant produces only about 1 GW, so the cable would absorb more power than whole power grids produce and melt.

  2. Step 2

    Pdiss=IrmsR2=(250 A)(4.00 Ω)2=(250)(16)=4000 WP_{\text{diss}} = I_{\text{rms}} R^2 = (250\text{ A})(4.00\,\Omega)^2 = (250)(16) = 4000\text{ W}

    Correct

    Pdiss=Irms2R=(250 A)2(4.00 Ω)=(6.25×104 A2)(4.00 Ω)=2.50×105 W=250 kWP_{\text{diss}} = I_{\text{rms}}^2 R = (250\text{ A})^2(4.00\,\Omega) = (6.25 \times 10^4\text{ A}^2)(4.00\,\Omega) = 2.50 \times 10^5\text{ W} = 250\text{ kW}

    You mistakenly squared the resistance RR instead of the current IrmsI_{\text{rms}}. By Joule's law, dissipated power is proportional to the square of current: Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R.

  3. Step 3

    Units: A Ω2=A (V/A)2=V2/A≠W\text{Units: } \text{A}\,\Omega^2 = \text{A}\,(\text{V}/\text{A})^2 = \text{V}^2/\text{A} \neq \text{W}

    Correct

    [I2R]=A2⋅Ω=A2⋅(VA)=A⋅V=(Cs)(JC)=Js=W[I^2 R] = \text{A}^2 \cdot \Omega = \text{A}^2 \cdot \left(\frac{\text{V}}{\text{A}}\right) = \text{A} \cdot \text{V} = \left(\frac{\text{C}}{\text{s}}\right)\left(\frac{\text{J}}{\text{C}}\right) = \frac{\text{J}}{\text{s}} = \text{W}

    You correctly noticed that the unit of your written expression IR2I R^2 is V2/A≠W\text{V}^2/\text{A} \neq \text{W}, but because the formula in Step 2 was transposed, you did not show that the intended formula I2RI^2 R reduces to watts.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly contextualized the order of magnitude of 3.60 GW3.60\text{ GW} by comparing it to commercial power plant outputs.

You correctly identified that the units of IR2I R^2 do not equal watts, demonstrating good unit-checking awareness.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Formula transcription error (swapped exponent)

You squared the resistance RR instead of the current II when applying Joule's law.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You recalled the variables in Joule's law (II and RR) but misplaced the power-of-two exponent onto resistance instead of current, then stopped when the dimensional check flagged an inconsistency rather than tracing it back to the formula.

REASONING PATH
Your ACEpath teacher’s suggested approach
Joule Heating Formula
  • P=I2R=(ΔV)2R=IΔVP = I^2 R = \frac{(\Delta V)^2}{R} = I \Delta V

  • Ensure the exponent of 22 is applied to current (I2RI^2 R) or to voltage drop ((ΔV)2/R(\Delta V)^2 / R), never to resistance (IR2I R^2).

Using Unit Checks to Fix Errors
  • If your calculated units do not match the target unit (here, W\text{W}), re-derive the formula from fundamental definitions.

  • When A Ω2\text{A}\,\Omega^2 fails to give watts, reconstruct P=IΔV=I(IR)=I2RP = I \Delta V = I(IR) = I^2 R to catch where the exponent belongs.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Write Joule's law with the square on current: Pdiss=Irms2RP_{\text{diss}} = I_{\text{rms}}^2 R.

  2. Substitute the values: Pdiss=(250 A)2⋅4.00 Ω=62,500 A2⋅4.00 ΩP_{\text{diss}} = (250\text{ A})^2 \cdot 4.00\,\Omega = 62{,}500\text{ A}^2 \cdot 4.00\,\Omega.

  3. Multiply to find the dissipated power: Pdiss=250,000 W=250 kWP_{\text{diss}} = 250{,}000\text{ W} = 250\text{ kW}.

  4. Verify the units: A2⋅Ω=A2⋅(V/A)=A⋅V=(C/s)(J/C)=J/s=W\text{A}^2 \cdot \Omega = \text{A}^2 \cdot (\text{V}/\text{A}) = \text{A} \cdot \text{V} = (\text{C}/\text{s})(\text{J}/\text{C}) = \text{J}/\text{s} = \text{W}.

Final answer

(a) 3.60 GW3.60\text{ GW} is physically absurd because typical large power plants only produce 1 to 2 GW1\text{ to }2\text{ GW}, so line dissipation would exceed total grid generation; (b) Pdiss=2.50×105 W=250 kWP_{\text{diss}} = 2.50 \times 10^5\text{ W} = 250\text{ kW}, and [I2R]=A2⋅Ω=W[I^2 R] = \text{A}^2 \cdot \Omega = \text{W}.

NEXT STEPS
Final Takeaways from Your Teacher
  • Always write down the algebraic formula before substituting numbers to verify the exponent is on current: P=I2RP = I^2 R.

  • When a dimensional check fails, treat it as a red flag to revisit your algebraic formula rather than completing the problem with an unverified unit.

Lock it in

Similar question

01

A heating element with resistance R=12.0 ΩR = 12.0\,\Omega draws an RMS current of Irms=10.0 AI_{\text{rms}} = 10.0\text{ A}. Calculate the potential drop ΔV\Delta V across the element and the thermal power PP dissipated, verifying the units of both.

Answer

ΔV=IR=(10.0 A)(12.0 Ω)=120 V\Delta V = I R = (10.0\text{ A})(12.0\,\Omega) = 120\text{ V} (units: A Ω=V\text{A}\,\Omega = \text{V}). P=I2R=(10.0 A)2(12.0 Ω)=1200 W=1.20 kWP = I^2 R = (10.0\text{ A})^2(12.0\,\Omega) = 1200\text{ W} = 1.20\text{ kW} (units: A2 Ω=A⋅V=W\text{A}^2\,\Omega = \text{A}\cdot\text{V} = \text{W}).

02

A high-voltage DC transmission line operates at a line-to-ground voltage of Vgrid=500 kVV_{\text{grid}} = 500\text{ kV} and delivers Ptransmitted=1000 MWP_{\text{transmitted}} = 1000\text{ MW} of power over wires of total resistance R=8.00 ΩR = 8.00\,\Omega. Determine the current II in the line, the line voltage drop ΔVline\Delta V_{\text{line}}, and the percentage of power lost as heat along the line.

Answer

Current: I=PtransmittedVgrid=109 W5×105 V=2000 AI = \frac{P_{\text{transmitted}}}{V_{\text{grid}}} = \frac{10^9\text{ W}}{5 \times 10^5\text{ V}} = 2000\text{ A}. Line voltage drop: ΔVline=IR=(2000 A)(8.00 Ω)=16.0 kV\Delta V_{\text{line}} = I R = (2000\text{ A})(8.00\,\Omega) = 16.0\text{ kV}. Dissipated power: Ploss=I2R=(2000 A)2(8.00 Ω)=3.20×107 W=32.0 MWP_{\text{loss}} = I^2 R = (2000\text{ A})^2(8.00\,\Omega) = 3.20 \times 10^7\text{ W} = 32.0\text{ MW}. Fractional loss: 32.0 MW1000 MW×100%=3.20%\frac{32.0\text{ MW}}{1000\text{ MW}} \times 100\% = 3.20\%, confirming that transmission line loss is a small fraction of grid power.

03

Show by unit breakdown in base SI units (kg\text{kg}, m\text{m}, s\text{s}, A\text{A}) that the three equivalent electrical power formulas P=IΔVP = I \Delta V, P=I2RP = I^2 R, and P=ΔV2RP = \frac{\Delta V^2}{R} all reduce identically to kg⋅m2⋅s−3\text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}.

Answer

In base SI units: V=J/C=kg⋅m2⋅s−2A⋅s=kg⋅m2⋅s−3⋅A−1\text{V} = \text{J}/\text{C} = \frac{\text{kg}\cdot\text{m}^2\cdot\text{s}^{-2}}{\text{A}\cdot\text{s}} = \text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}\cdot\text{A}^{-1}, and Ω=V/A=kg⋅m2⋅s−3⋅A−2\Omega = \text{V}/\text{A} = \text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}\cdot\text{A}^{-2}. Thus: (1) [IΔV]=A⋅(kg⋅m2⋅s−3⋅A−1)=kg⋅m2⋅s−3[I \Delta V] = \text{A} \cdot (\text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}\cdot\text{A}^{-1}) = \text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}. (2) [I2R]=A2⋅(kg⋅m2⋅s−3⋅A−2)=kg⋅m2⋅s−3[I^2 R] = \text{A}^2 \cdot (\text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}\cdot\text{A}^{-2}) = \text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}. (3) [ΔV2/R]=(kg2⋅m4⋅s−6⋅A−2)/(kg⋅m2⋅s−3⋅A−2)=kg⋅m2⋅s−3=W[\Delta V^2 / R] = (\text{kg}^2\cdot\text{m}^4\cdot\text{s}^{-6}\cdot\text{A}^{-2}) / (\text{kg}\cdot\text{m}^2\cdot\text{s}^{-3}\cdot\text{A}^{-2}) = \text{kg}\cdot\text{m}^2\cdot\text{s}^{-3} = \text{W}.