A commercial cold-storage warehouse refrigeration unit operates with an electric compressor rated at a continuous power input of P=4.50 hp\mathcal{P} = 4.50\text{ hp} (1 hp=746 W1\text{ hp} = 746\text{ W}). The refrigeration system maintains the internal warehouse freezing locker at TC=−20.0∘CT_C = -20.0^\circ\text{C} and has an actual coefficient of performance of COP=2.40\text{COP} = 2.40. The system is used to freeze liquid water initially at 0.0∘C0.0^\circ\text{C} into solid ice at 0.0∘C0.0^\circ\text{C}. The latent heat of fusion of water is Lf=3.33×105 J/kgL_f = 3.33 \times 10^5\text{ J/kg}. Calculate: (a) the mechanical work delivered by the compressor in kilowatt-hours (kW⋅h\text{kW}\cdot\text{h}) over an operational duration of Δt=2.00 h\Delta t = 2.00\text{ h}, (b) the total thermal energy extracted from the cold space ∣QC∣|Q_C| in megajoules (MJ\text{MJ}), and (c) the total mass of ice produced micem_{\text{ice}} in kilograms over this 2.00 h2.00\text{ h} period.

Answer and steps

Final answer

(a) Win=6.71 kW⋅hW_{\text{in}} = 6.71\text{ kW}\cdot\text{h} (2.42×107 J2.42 \times 10^7\text{ J}); (b) ∣QC∣=58.0 MJ|Q_C| = 58.0\text{ MJ} (5.80×107 J5.80 \times 10^7\text{ J}); (c) mice=174 kgm_{\text{ice}} = 174\text{ kg}.

Steps

Part (a): Mechanical Work Input

  1. Convert the compressor's power rating to kilowatts (kW\text{kW}): The power input P\mathcal{P} is given in horsepower: P=4.50 hp×746 W/hp=3357 W=3.357 kW\mathcal{P} = 4.50\text{ hp} \times 746\text{ W/hp} = 3357\text{ W} = 3.357\text{ kW}
  2. Calculate the work delivered over Δt=2.00 h\Delta t = 2.00\text{ h}: Work is the product of continuous power and operating time: Win=P⋅Δt=3.357 kW⋅2.00 h≈6.71 kW⋅hW_{\text{in}} = \mathcal{P} \cdot \Delta t = 3.357\text{ kW} \cdot 2.00\text{ h} \approx 6.71\text{ kW}\cdot\text{h}

    Converting this quantity into joules (J\text{J}): Win=3357 J/s×(2.00×3600 s)=2.417×107 J≈2.42×107 JW_{\text{in}} = 3357\text{ J/s} \times (2.00 \times 3600\text{ s}) = 2.417 \times 10^7\text{ J} \approx 2.42 \times 10^7\text{ J}


Part (b): Thermal Energy Extracted from the Cold Space

  1. Apply the definition of the Coefficient of Performance (COP\text{COP}): For a refrigeration cycle, the coefficient of performance is the ratio of heat removed from the cold reservoir (∣QC∣|Q_C|) to the work input required (WinW_{\text{in}}): COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}
  2. Solve for the extracted heat ∣QC∣|Q_C|: ∣QC∣=COP⋅Win=2.40⋅(2.417×107 J)≈5.80×107 J=58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \cdot (2.417 \times 10^7\text{ J}) \approx 5.80 \times 10^7\text{ J} = 58.0\text{ MJ}

Common Pitfall: Do not use the theoretical Carnot maximum COPCarnot=TCTH−TC\text{COP}_{\text{Carnot}} = \frac{T_C}{T_H - T_C} when an actual, measured COP\text{COP} is explicitly provided. Real refrigeration systems experience irreversibilities and operate below the ideal Carnot limit.


Part (c): Total Mass of Ice Produced

  1. Relate extracted heat to the phase change of water: The water is already at its freezing point (0.0∘C0.0^\circ\text{C}), so all thermal energy extracted directly drives the phase change from liquid to solid without requiring sensible cooling: ∣QC∣=miceLf|Q_C| = m_{\text{ice}} L_f
  2. Solve for the mass of ice formed, micem_{\text{ice}}: mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}

Typical errors

OverviewACEpath Teacher's Diagnosis

01 The student confuses the coefficient of performance definition by dividing work by COP instead of multiplying, underestimating the heat extracted and ice produced.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    P=4.50×746 W=3357 W=3.357 kW  ⟹  W=3.357 kW×2.00 h=6.714 kW⋅h  ⟹  W=6.714×3.6×106 J=24.17 MJ\mathcal{P} = 4.50 \times 746\text{ W} = 3357\text{ W} = 3.357\text{ kW} \implies W = 3.357\text{ kW} \times 2.00\text{ h} = 6.714\text{ kW}\cdot\text{h} \implies W = 6.714 \times 3.6 \times 10^6\text{ J} = 24.17\text{ MJ}

  2. Step 2

    ∣QC∣=WCOP=24.17 MJ2.40=10.07 MJ|Q_C| = \frac{W}{\text{COP}} = \frac{24.17\text{ MJ}}{2.40} = 10.07\text{ MJ}

    Correct

    ∣QC∣=COP⋅Win=2.40×24.17 MJ≈58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \times 24.17\text{ MJ} \approx 58.0\text{ MJ}

    For a refrigerator, the coefficient of performance is defined as the benefit divided by the cost, COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}. Solving for the heat extracted requires multiplying work by COP\text{COP} (∣QC∣=COP⋅Win|Q_C| = \text{COP} \cdot W_{\text{in}}), not dividing.

  3. Step 3

    mice=∣QC∣Lf=1.007×107 J3.33×105 J/kg=30.2 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{1.007 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} = 30.2\text{ kg}

    Correct

    mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}

    Your latent heat formula and algebraic substitution were completely correct, but the numerical answer was affected by the underestimated ∣QC∣|Q_C| from the previous step.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly converted horsepower to watts and calculated total work input in both kilowatt-hours and megajoules.

You correctly identified that the freezing process at 0.0∘C0.0^\circ\text{C} relates heat removal to latent heat via ∣QC∣=miceLf|Q_C| = m_{\text{ice}} L_f.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Inverted Coefficient of Performance Definition

You divided work by COP\text{COP} rather than multiplying by COP\text{COP} when solving for the heat extracted ∣QC∣|Q_C|.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You likely confused the performance metric of a refrigerator with heat engine thermal efficiency (η=WQH<1\eta = \frac{W}{Q_H} < 1). A refrigerator's COP\text{COP} represents the ratio of heat extracted from the cold space to the work input required (COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}), which is often greater than 11, meaning the heat extracted exceeds the work supplied.

REASONING PATH
Your ACEpath teacher’s suggested approach
Benefit over Cost Principle
  • For any cyclic device, performance is defined as What You GetWhat You Pay For\frac{\text{What You Get}}{\text{What You Pay For}}.

  • For a refrigerator, you want cooling (∣QC∣|Q_C|) and you pay with compressor work (WinW_{\text{in}}), so COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}, giving ∣QC∣=COP⋅Win|Q_C| = \text{COP} \cdot W_{\text{in}}.

Magnitude Reality Check
  • Modern refrigeration cycles typically have COP>1\text{COP} > 1.

  • Since COP>1\text{COP} > 1, the heat extracted ∣QC∣|Q_C| must be strictly greater than the electrical/mechanical work input WinW_{\text{in}}.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Apply the standard refrigeration formula: ∣QC∣=COP⋅Win|Q_C| = \text{COP} \cdot W_{\text{in}}.

  2. Substitute the work from part (a): ∣QC∣=2.40×2.417×107 J≈5.80×107 J=58.0 MJ|Q_C| = 2.40 \times 2.417 \times 10^7\text{ J} \approx 5.80 \times 10^7\text{ J} = 58.0\text{ MJ}.

  3. Calculate the mass of ice: mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}.

Final answer

(a) Win=6.71 kW⋅hW_{\text{in}} = 6.71\text{ kW}\cdot\text{h}; (b) ∣QC∣=58.0 MJ|Q_C| = 58.0\text{ MJ}; (c) mice=174 kgm_{\text{ice}} = 174\text{ kg}

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the fundamental distinction between heat engine efficiency η=WoutQH\eta = \frac{W_{\text{out}}}{Q_H} and refrigerator coefficient of performance COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}.

  • Practice solving for each variable (∣QC∣|Q_C|, WinW_{\text{in}}, and ∣QH∣|Q_H|) in both ideal and real refrigeration cycles.

OverviewACEpath Teacher's Diagnosis

02 The student miscalculates the work in part (a) by multiplying power by 3600 seconds instead of hours, giving work in kW·s rather than kW·h.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    P=4.50×0.746 kW=3.357 kW  ⟹  Δt=2.00×3600 s=7200 s  ⟹  W=3.357 kW×7200 s=24170 kW⋅h  ⟹  W=24170 kW⋅h×3.60×106 J/(kW⋅h)=8.701×1010 J=87010 MJP = 4.50 \times 0.746\text{ kW} = 3.357\text{ kW} \implies \Delta t = 2.00 \times 3600\text{ s} = 7200\text{ s} \implies W = 3.357\text{ kW} \times 7200\text{ s} = 24170\text{ kW}\cdot\text{h} \implies W = 24170\text{ kW}\cdot\text{h} \times 3.60 \times 10^6\text{ J/(kW}\cdot\text{h)} = 8.701 \times 10^{10}\text{ J} = 87010\text{ MJ}

    Correct

    Win=P⋅Δt=3.357 kW×2.00 h=6.71 kW⋅h  ⟹  Win=6.714 kW⋅h×3.60×106 J/(kW⋅h)=2.42×107 JW_{\text{in}} = \mathcal{P} \cdot \Delta t = 3.357\text{ kW} \times 2.00\text{ h} = 6.71\text{ kW}\cdot\text{h} \implies W_{\text{in}} = 6.714\text{ kW}\cdot\text{h} \times 3.60 \times 10^6\text{ J/(kW}\cdot\text{h)} = 2.42 \times 10^7\text{ J}

    You correctly converted horsepower to kilowatts (3.357 kW3.357\text{ kW}), but you multiplied kilowatts by seconds (7200 s7200\text{ s}) and labeled the product as kW⋅h\text{kW}\cdot\text{h}. Multiplying kW\text{kW} by seconds yields kilojoules (kJ\text{kJ}), not kW⋅h\text{kW}\cdot\text{h}. To obtain energy in kW⋅h\text{kW}\cdot\text{h}, keep the time in hours: 3.357 kW×2.00 h=6.71 kW⋅h3.357\text{ kW} \times 2.00\text{ h} = 6.71\text{ kW}\cdot\text{h}.

  2. Step 2

    ∣QC∣=COP×W=2.40×87010 MJ=208824 MJ|Q_C| = \text{COP} \times W = 2.40 \times 87010\text{ MJ} = 208824\text{ MJ}

    Correct

    ∣QC∣=COP⋅Win=2.40×2.417×107 J≈5.80×107 J=58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \times 2.417 \times 10^7\text{ J} \approx 5.80 \times 10^7\text{ J} = 58.0\text{ MJ}

    Your formula ∣QC∣=COP⋅W|Q_C| = \text{COP} \cdot W is completely correct. This step is only incorrect because it inherits the inflated work value from Part (a).

  3. Step 3

    mice=∣QC∣Lf=2.088×1011 J3.33×105 J/kg=6.27×105 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{2.088 \times 10^{11}\text{ J}}{3.33 \times 10^5\text{ J/kg}} = 6.27 \times 10^5\text{ kg}

    Correct

    mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}

    Your application of the phase-change formula m=∣QC∣Lfm = \frac{|Q_C|}{L_f} is correct. The resulting mass is incorrect solely due to carrying forward the erroneous value of ∣QC∣|Q_C|.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly converted horsepower to kilowatts using the given conversion factor.

You correctly related refrigeration heat extraction to work input using COP=∣QC∣W\text{COP} = \frac{|Q_C|}{W}.

You correctly applied the latent heat equation ∣QC∣=mLf|Q_C| = m L_f to compute the mass of ice.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Unit Conversion Error

Treating the product of power in kilowatts and time in seconds as kilowatt-hours instead of kilojoules.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Confusion between compound time units and SI base units during energy calculations. A kilowatt-hour requires multiplying power in kW\text{kW} directly by time in hours (h\text{h}), whereas multiplying kW\text{kW} by seconds yields kilojoules (kJ\text{kJ}). Converting hours to seconds first and then labeling the result as kW⋅h\text{kW}\cdot\text{h} causes a double conversion by an extra factor of 36003600.

REASONING PATH
Your ACEpath teacher’s suggested approach
Compound Units vs. SI Base Units
  • 1 kW⋅h=1 kW×1 h=3.60×106 J1\text{ kW}\cdot\text{h} = 1\text{ kW} \times 1\text{ h} = 3.60 \times 10^6\text{ J}, whereas 1 kW×1 s=1 kJ=103 J1\text{ kW} \times 1\text{ s} = 1\text{ kJ} = 10^3\text{ J}.

  • Whenever energy is requested in kW⋅h\text{kW}\cdot\text{h}, keep the time in hours ( t in h\,t\text{ in h}). If energy is needed in Joules, either convert time to seconds (t in st\text{ in s}) and use Watts, or multiply kW⋅h\text{kW}\cdot\text{h} by 3.60×106 J/(kW⋅h)3.60 \times 10^6\text{ J/(kW}\cdot\text{h)}.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Compute work in kW⋅h\text{kW}\cdot\text{h} directly: Win=3.357 kW×2.00 h=6.714 kW⋅h≈6.71 kW⋅hW_{\text{in}} = 3.357\text{ kW} \times 2.00\text{ h} = 6.714\text{ kW}\cdot\text{h} \approx 6.71\text{ kW}\cdot\text{h}.

  2. Convert work to Joules: Win=6.714 kW⋅h×3.60×106 J/(kW⋅h)=2.417×107 JW_{\text{in}} = 6.714\text{ kW}\cdot\text{h} \times 3.60 \times 10^6\text{ J/(kW}\cdot\text{h)} = 2.417 \times 10^7\text{ J}.

  3. Calculate heat removed: ∣QC∣=COP⋅Win=2.40×2.417×107 J=5.801×107 J=58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \times 2.417 \times 10^7\text{ J} = 5.801 \times 10^7\text{ J} = 58.0\text{ MJ}.

  4. Calculate mass of ice: mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}.

Final answer

(a) Win=6.71 kW⋅hW_{\text{in}} = 6.71\text{ kW}\cdot\text{h} (2.42×107 J2.42 \times 10^7\text{ J}); (b) ∣QC∣=58.0 MJ|Q_C| = 58.0\text{ MJ}; (c) mice=174 kgm_{\text{ice}} = 174\text{ kg}.

NEXT STEPS
Final Takeaways from Your Teacher
  • Always write down the units explicitly in each intermediate multiplication step (e.g., kW×s=kJ\text{kW} \times \text{s} = \text{kJ}) to verify that your resulting units match the target unit before converting further.

  • Practice identifying whether a question asks for energy in standard SI units (Joules) or utility units (kilowatt-hours) before choosing your time conversion strategy.

OverviewACEpath Teacher's Diagnosis

03 The student erroneously uses the ideal Carnot COP formula based on temperature instead of the stated actual COP of 2.40.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    P=4.50×0.746 kW=3.357 kW  ⟹  W=3.357 kW×2.00 h=6.714 kW⋅h  ⟹  W=6.714×3.60×106 J=24.17 MJP = 4.50 \times 0.746\text{ kW} = 3.357\text{ kW} \implies W = 3.357\text{ kW} \times 2.00\text{ h} = 6.714\text{ kW}\cdot\text{h} \implies W = 6.714 \times 3.60 \times 10^6\text{ J} = 24.17\text{ MJ}

  2. Step 2

    TC=−20.0+273.15=253.15 K  ⟹  TH=0.0+273.15=273.15 K  ⟹  COP=TCTH−TC=253.1520.0=12.66  ⟹  ∣QC∣=COP×W=12.66×24.17 MJ=306 MJT_C = -20.0 + 273.15 = 253.15\text{ K} \implies T_H = 0.0 + 273.15 = 273.15\text{ K} \implies \text{COP} = \frac{T_C}{T_H - T_C} = \frac{253.15}{20.0} = 12.66 \implies |Q_C| = \text{COP} \times W = 12.66 \times 24.17\text{ MJ} = 306\text{ MJ}

    Correct

    ∣QC∣=COP⋅Win=2.40⋅24.17 MJ≈58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \cdot 24.17\text{ MJ} \approx 58.0\text{ MJ}

    The problem directly specifies an actual performance rating of COP=2.40\text{COP} = 2.40. Calculating COPCarnot=TCTH−TC\text{COP}_{\text{Carnot}} = \frac{T_C}{T_H - T_C} gives the theoretical upper limit for a reversible cycle, not the performance of this real warehouse refrigeration unit.

  3. Step 3

    mice=∣QC∣Lf=3.06×108 J3.33×105 J/kg=919 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{3.06 \times 10^8\text{ J}}{3.33 \times 10^5\text{ J/kg}} = 919\text{ kg}

    Correct

    mice=∣QC∣Lf=5.80×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.80 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}

    Your formula relating heat removal to latent heat of fusion is correct, but substituting the incorrect value of ∣QC∣|Q_C| led to an incorrect numerical result.

WHAT YOU DID WELL
Compliments from Your Teacher

You converted horsepower into kilowatts and found the total mechanical work delivered in both kilowatt-hours and megajoules correctly.

You correctly recognized that the extracted heat relates to the mass of frozen ice through the latent heat equation ∣QC∣=miceLf|Q_C| = m_{\text{ice}} L_f.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Carnot COP vs. Actual COP

No slip occurred; this was a conceptual selection of the Carnot formula instead of using the provided actual COP.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You defaulted to calculating the ideal Carnot coefficient of performance from reservoir temperatures instead of using the actual coefficient of performance explicitly stated in the problem statement.

REASONING PATH
Your ACEpath teacher’s suggested approach
Check for Given Operating Specifications
  • When an actual coefficient of performance (COP\text{COP}) is provided, use it directly to relate heat and work via ∣QC∣=COP⋅Win|Q_C| = \text{COP} \cdot W_{\text{in}}.

  • Always scan the problem for explicitly given actual performance ratings before reaching for ideal Carnot formulas.

Distinguish Ideal Limits from Real Devices
  • The temperature-based formula COPCarnot=TCTH−TC\text{COP}_{\text{Carnot}} = \frac{T_C}{T_H - T_C} represents the maximum theoretical upper bound, which real machines with friction and irreversibilities cannot achieve.

  • Use reservoir temperatures to compute COP\text{COP} only when the problem specifically asks for the maximum theoretical efficiency or ideal Carnot performance.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Use the given actual coefficient of performance COP=2.40\text{COP} = 2.40 directly with the definition COP=∣QC∣Win\text{COP} = \frac{|Q_C|}{W_{\text{in}}}.

  2. Solve for the extracted heat: ∣QC∣=COP⋅Win=2.40⋅24.17 MJ≈58.0 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.40 \cdot 24.17\text{ MJ} \approx 58.0\text{ MJ}.

  3. Calculate the mass of ice using the corrected heat value: mice=∣QC∣Lf=5.801×107 J3.33×105 J/kg≈174 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{5.801 \times 10^7\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 174\text{ kg}.

Final answer

(a) Win=6.71 kW⋅hW_{\text{in}} = 6.71\text{ kW}\cdot\text{h} (2.42×107 J2.42 \times 10^7\text{ J}); (b) ∣QC∣=58.0 MJ|Q_C| = 58.0\text{ MJ}; (c) mice=174 kgm_{\text{ice}} = 174\text{ kg}.

NEXT STEPS
Final Takeaways from Your Teacher
  • Read the problem statement carefully to see if an empirical or actual COP is already supplied before writing down temperature formulas.

  • Practice identifying whether a question asks for the theoretical Carnot maximum or describes a real, practical thermodynamic cycle.

Lock it in

Similar question

01

A household refrigerator has an operating COP=1.80\text{COP} = 1.80. If the motor supplies 1.50×106 J1.50 \times 10^6\text{ J} of mechanical work during a cooling cycle, calculate the heat removed from the food compartment in megajoules (MJ\text{MJ}).

Answer

∣QC∣=2.70 MJ|Q_C| = 2.70\text{ MJ}. Key steps: ∣QC∣=COP⋅Win=1.80×(1.50×106 J)=2.70×106 J=2.70 MJ|Q_C| = \text{COP} \cdot W_{\text{in}} = 1.80 \times (1.50 \times 10^6\text{ J}) = 2.70 \times 10^6\text{ J} = 2.70\text{ MJ}.

02

A commercial chiller extracts 120 MJ120\text{ MJ} of heat from a cold bath over a 1.00 h1.00\text{ h} run. If the system operates with COP=2.50\text{COP} = 2.50, find the average electrical power consumed by the compressor in kilowatts (kW\text{kW}).

Answer

P=13.3 kW\mathcal{P} = 13.3\text{ kW}. Key steps: Win=∣QC∣COP=120 MJ2.50=48.0 MJW_{\text{in}} = \frac{|Q_C|}{\text{COP}} = \frac{120\text{ MJ}}{2.50} = 48.0\text{ MJ}; then P=WinΔt=4.80×107 J3600 s≈1.33×104 W=13.3 kW\mathcal{P} = \frac{W_{\text{in}}}{\Delta t} = \frac{4.80 \times 10^7\text{ J}}{3600\text{ s}} \approx 1.33 \times 10^4\text{ W} = 13.3\text{ kW}.

03

A freezer with COP=2.20\text{COP} = 2.20 is powered by a 250 W250\text{ W} motor running continuously for 4.00 h4.00\text{ h}. If water at 0.0∘C0.0^\circ\text{C} is placed inside, what mass of water can be converted into ice at 0.0∘C0.0^\circ\text{C}? (Take Lf=3.33×105 J/kgL_f = 3.33 \times 10^5\text{ J/kg}).

Answer

mice≈23.8 kgm_{\text{ice}} \approx 23.8\text{ kg}. Key steps: Total work Win=P⋅Δt=(250 W)(14400 s)=3.60×106 JW_{\text{in}} = \mathcal{P} \cdot \Delta t = (250\text{ W})(14400\text{ s}) = 3.60 \times 10^6\text{ J}. Heat extracted ∣QC∣=COP⋅Win=2.20×3.60×106 J=7.92×106 J|Q_C| = \text{COP} \cdot W_{\text{in}} = 2.20 \times 3.60 \times 10^6\text{ J} = 7.92 \times 10^6\text{ J}. Ice mass mice=∣QC∣Lf=7.92×106 J3.33×105 J/kg≈23.8 kgm_{\text{ice}} = \frac{|Q_C|}{L_f} = \frac{7.92 \times 10^6\text{ J}}{3.33 \times 10^5\text{ J/kg}} \approx 23.8\text{ kg}.