In a physics engineering laboratory, an AC generator test bench uses a multi-turn armature driven by a variable-speed motor inside a field created by electromagnets. The generator output feeds an experimental toroidal transformer to calibrate line losses. The data acquisition system records: primary input voltage Vp=48.0 V (rms)V_p = 48.0\text{ V (rms)}, primary input current Ip=2.50 A (rms)I_p = 2.50\text{ A (rms)}, and primary phase angle ϕp=18.2∘\phi_p = 18.2^\circ (current lags voltage). Across the secondary terminals, a precision digital power analyzer records a load voltage of Vs=184 V (rms)V_s = 184\text{ V (rms)} across a purely resistive load box drawing Is=0.550 A (rms)I_s = 0.550\text{ A (rms)}. (a) Compute the real input power PinP_{\text{in}} delivered to the transformer primary. (b) Determine the transformer efficiency η\eta under these experimental test bench conditions.

Answer and steps

Final answer

(a) Pin=114 WP_{\text{in}} = 114\text{ W}; (b) η=88.8%\eta = 88.8\%

Steps

Part (a): Real Input Power Delivered to the Primary

In an alternating current (AC\text{AC}) circuit, real (average) power accounts for the phase difference between the voltage and current waveforms. The formula for the real input power PinP_{\text{in}} is:

Pin=VpIpcos⁡ϕpP_{\text{in}} = V_p I_p \cos\phi_p

where:

  • Vp=48.0 VV_p = 48.0\text{ V} is the root-mean-square (rms\text{rms}) primary voltage,
  • Ip=2.50 AI_p = 2.50\text{ A} is the rms\text{rms} primary current,
  • ϕp=18.2∘\phi_p = 18.2^\circ is the phase angle by which the current lags the voltage,
  • cos⁡ϕp\cos\phi_p is the primary power factor.

Calculate the power factor: cos⁡(18.2∘)≈0.9500\cos(18.2^\circ) \approx 0.9500

Substitute the values: Pin=(48.0 V)⋅(2.50 A)⋅cos⁡(18.2∘)=120.0⋅0.9500=114 WP_{\text{in}} = (48.0\text{ V}) \cdot (2.50\text{ A}) \cdot \cos(18.2^\circ) = 120.0 \cdot 0.9500 = 114\text{ W}

Common Pitfall: Do not simply multiply Vp⋅IpV_p \cdot I_p. That gives the apparent power SS in volt-amperes (VA\text{VA}), which overestimates the useful real power entering an inductive or reactive component.


Part (b): Transformer Efficiency Under Test Conditions

  1. Calculate the Output Power (PoutP_{\text{out}}): The secondary circuit is connected to a purely resistive load, meaning the voltage and current are in phase (ϕs=0∘\phi_s = 0^\circ, so cos⁡ϕs=1\cos\phi_s = 1).

    Pout=VsIscos⁡ϕs=(184 V)⋅(0.550 A)⋅1=101.2 WP_{\text{out}} = V_s I_s \cos\phi_s = (184\text{ V}) \cdot (0.550\text{ A}) \cdot 1 = 101.2\text{ W}

  2. Calculate Efficiency (η\eta): The efficiency of the transformer is the ratio of real power delivered to the load to the real power supplied to the primary:

    η=PoutPin×100%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\%

    Substitute the values: η=101.2 W114 W×100%≈88.77%≈88.8%\eta = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.77\% \approx 88.8\%

Typical errors

OverviewACEpath Teacher's Diagnosis

01 The student ignores the primary power factor cos(phi_p) and equates real input power to apparent power V_p * I_p, leading to an underestimated efficiency.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Pin=Vp⋅Ip=(48.0 V)(2.50 A)=120 WP_{\text{in}} = V_p \cdot I_p = (48.0\text{ V})(2.50\text{ A}) = 120\text{ W}

    Correct

    Pin=VpIpcos⁡ϕp=(48.0 V)(2.50 A)cos⁡(18.2∘)=114 WP_{\text{in}} = V_p I_p \cos\phi_p = (48.0\text{ V})(2.50\text{ A})\cos(18.2^\circ) = 114\text{ W}

    In an AC circuit where current and voltage are out of phase, the product VpIpV_p I_p represents apparent power SS in volt-amperes, not real power. To find the real power delivered to the primary, you must multiply by the power factor cos⁡ϕp\cos\phi_p.

  2. Step 2

    Pout=Vs⋅Is=(184 V)(0.550 A)=101.2 WP_{\text{out}} = V_s \cdot I_s = (184\text{ V})(0.550\text{ A}) = 101.2\text{ W}

  3. Step 3

    η=PoutPin=101.2 W120 W=84.3%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} = \frac{101.2\text{ W}}{120\text{ W}} = 84.3\%

    Correct

    η=PoutPin=101.2 W114 W×100%≈88.8%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.8\%

    Your efficiency formula and division are mathematically sound, but using the incorrect input power of 120 W120\text{ W} from Step 1 caused the resulting efficiency to be lower than the true value.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly recognized that the output load is purely resistive, making cos⁡ϕs=1\cos\phi_s = 1 when finding PoutP_{\text{out}}.

You correctly applied the ratio formula for transformer efficiency, η=PoutPin×100%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\%.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Omission of AC Power Factor

no

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Confusing apparent power S=VIS = V I with real (active) power P=VIcos⁡ϕP = V I \cos\phi in reactive AC circuits.

REASONING PATH
Your ACEpath teacher’s suggested approach
Real Power vs. Apparent Power
  • Real power in single-phase AC is given by P=VrmsIrmscos⁡ϕP = V_{\text{rms}} I_{\text{rms}} \cos\phi, where cos⁡ϕ\cos\phi is the power factor.

  • Check if a phase angle ϕ\phi or power factor is specified whenever an AC circuit contains inductive or capacitive elements.

Transformer Primary Inductance
  • Transformer coils have inherent self-inductance and magnetizing currents that create a phase shift between primary voltage and current.

  • Always multiply the primary volt-amperes by cos⁡ϕp\cos\phi_p when evaluating input real power unless a unity power factor is explicitly stated.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Include the primary phase angle ϕp=18.2∘\phi_p = 18.2^\circ: Pin=VpIpcos⁡ϕp=(48.0 V)(2.50 A)cos⁡(18.2∘)P_{\text{in}} = V_p I_p \cos\phi_p = (48.0\text{ V})(2.50\text{ A})\cos(18.2^\circ).

  2. Evaluate the real input power: Pin=120.0×0.9500=114 WP_{\text{in}} = 120.0 \times 0.9500 = 114\text{ W}.

  3. Recalculate efficiency using the corrected real input power: η=101.2 W114 W×100%≈88.8%\eta = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.8\%.

Final answer

(a) Pin=114 WP_{\text{in}} = 114\text{ W}; (b) η=88.8%\eta = 88.8\%

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the distinction between apparent power (SS, in VA\text{VA}), reactive power (QQ, in VAR\text{VAR}), and real power (PP, in W\text{W}).

  • Practice identifying when a circuit element has a non-zero phase angle ϕ\phi before calculating energy or efficiency.

OverviewACEpath Teacher's Diagnosis

02 The student calculates the phase angle in radians while treating the numerical degree value as radians with sin(phi_p) instead of cos(phi_p), computing reactive power instead of real input power.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Pin=Vp∗Ip∗sin⁡(18.2∘)  ⟹  Pin=(48.0 V)(2.50 A)∗0.3123=37.5 WP_{\text{in}} = V_p * I_p * \sin(18.2^\circ) \implies P_{\text{in}} = (48.0\text{ V})(2.50\text{ A}) * 0.3123 = 37.5\text{ W}

    Correct

    Pin=VpIpcos⁡(ϕp)=(48.0 V)(2.50 A)cos⁡(18.2∘)≈114 WP_{\text{in}} = V_p I_p \cos(\phi_p) = (48.0\text{ V})(2.50\text{ A}) \cos(18.2^\circ) \approx 114\text{ W}

    Real (active) power in an AC circuit is determined by the power factor cos⁡ϕ\cos\phi, not sin⁡ϕ\sin\phi. Multiplying by sin⁡ϕ\sin\phi calculates the reactive power QQ in volt-amperes reactive (VAR), rather than the real power PP in watts.

  2. Step 2

    Pout=Vs∗Is=(184 V)(0.550 A)=101.2 WP_{\text{out}} = V_s * I_s = (184\text{ V})(0.550\text{ A}) = 101.2\text{ W}

  3. Step 3

    η=PoutPin=101.2 W37.5 W=270%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} = \frac{101.2\text{ W}}{37.5\text{ W}} = 270\%

    Correct

    η=PoutPin×100%=101.2 W114 W×100%≈88.8%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\% = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.8\%

    Your efficiency formula is conceptually correct, but substituting the incorrect reactive power for PinP_{\text{in}} produced an unphysical efficiency over 100%100\%.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly calculated the secondary real output power Pout=101.2 WP_{\text{out}} = 101.2\text{ W} for the resistive load.

You correctly stated the definition of efficiency as the ratio of output power to input power η=PoutPin\eta = \frac{P_{\text{out}}}{P_{\text{in}}}.

You accurately evaluated numerical arithmetic for the expressions you wrote.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Trigonometric function confusion (real vs. reactive power)

You used sin⁡ϕ\sin\phi instead of cos⁡ϕ\cos\phi when calculating the input power.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You confused active (real) power P=VIcos⁡ϕP = V I \cos\phi with reactive power Q=VIsin⁡ϕQ = V I \sin\phi. In AC circuit analysis, the in-phase component of current that produces useful real work is proportional to the cosine of the phase angle (the power factor).

REASONING PATH
Your ACEpath teacher’s suggested approach
Real Power vs. Reactive Power
  • Real power delivered is P=VrmsIrmscos⁡ϕP = V_{\text{rms}} I_{\text{rms}} \cos\phi, while reactive power is Q=VrmsIrmssin⁡ϕQ = V_{\text{rms}} I_{\text{rms}} \sin\phi.

  • Always associate real power (watts) with cos⁡ϕ\cos\phi and reactive power (VAR) with sin⁡ϕ\sin\phi.

Conservation of Energy Sanity Check
  • For any passive electrical component or transformer, output power cannot exceed input power, meaning efficiency must satisfy η≤100%\eta \le 100\%.

  • If a computed efficiency exceeds 100%100\%, pause and re-examine whether input power was underestimated or calculated using reactive power.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Pin=VpIpcos⁡(ϕp)=(48.0 V)(2.50 A)cos⁡(18.2∘)=120.0×0.9500=114 WP_{\text{in}} = V_p I_p \cos(\phi_p) = (48.0\text{ V})(2.50\text{ A})\cos(18.2^\circ) = 120.0 \times 0.9500 = 114\text{ W}

  2. η=PoutPin×100%=101.2 W114 W×100%≈88.8%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\% = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.8\%

Final answer

(a) Pin=114 WP_{\text{in}} = 114\text{ W}; (b) η=88.8%\eta = 88.8\%

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the AC power triangle to visually anchor active power on the adjacent axis (P=Scos⁡ϕP = S\cos\phi) and reactive power on the opposite axis (Q=Ssin⁡ϕQ = S\sin\phi).

  • Whenever you obtain an efficiency greater than 100%100\% for a transformer, treat it as an automatic check to verify the real power formula.

OverviewACEpath Teacher's Diagnosis

03 The student calculates efficiency inverted as input power divided by output power, obtaining an efficiency greater than 100%.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Pin=Vp⋅Ip⋅cos⁡(18.2∘)  ⟹  Pin=(48.0 V)(2.50 A)⋅0.9500=114 WP_{\text{in}} = V_p \cdot I_p \cdot \cos(18.2^\circ) \implies P_{\text{in}} = (48.0\text{ V})(2.50\text{ A}) \cdot 0.9500 = 114\text{ W}

  2. Step 2

    Pout=Vs⋅Is=(184 V)(0.550 A)=101.2 WP_{\text{out}} = V_s \cdot I_s = (184\text{ V})(0.550\text{ A}) = 101.2\text{ W}

  3. Step 3

    η=PinPout=114 W101.2 W=113%\eta = \frac{P_{\text{in}}}{P_{\text{out}}} = \frac{114\text{ W}}{101.2\text{ W}} = 113\%

    Correct

    η=PoutPin×100%=101.2 W114 W×100%≈88.8%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\% = \frac{101.2\text{ W}}{114\text{ W}} \times 100\% \approx 88.8\%

    You placed input power in the numerator and output power in the denominator. Efficiency is always the ratio of useful output to total input, η=PoutPin\eta = \frac{P_{\text{out}}}{P_{\text{in}}}, which cannot exceed 100%100\% for a passive transformer.

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly included the primary phase angle ϕp\phi_p to calculate the real input power rather than apparent power.

You accurately calculated the secondary real power delivered to the resistive load.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Inverted efficiency ratio

no

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You defined efficiency as inputoutput\frac{\text{input}}{\text{output}} rather than outputinput\frac{\text{output}}{\text{input}}, overlooking that conservation of energy requires the useful output power of a passive device to be less than or equal to the supplied input power.

REASONING PATH
Your ACEpath teacher’s suggested approach
Definition of Efficiency
  • η=PoutPin×100%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\%

  • Always verify that the useful output is in the numerator and the total input supplied is in the denominator.

Sanity Check via Conservation of Energy
  • For any passive system with losses, Pout<PinP_{\text{out}} < P_{\text{in}}, so η<100%\eta < 100\%.

  • If your calculated efficiency exceeds 100%100\%, check whether you inverted the ratio.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Write the definition of efficiency: η=PoutPin×100%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\%.

  2. Substitute Pout=101.2 WP_{\text{out}} = 101.2\text{ W} and Pin=114 WP_{\text{in}} = 114\text{ W}: η=101.2 W114 W×100%\eta = \frac{101.2\text{ W}}{114\text{ W}} \times 100\%.

  3. Evaluate the percentage: η≈88.77%≈88.8%\eta \approx 88.77\% \approx 88.8\%.

Final answer

(a) Pin=114 WP_{\text{in}} = 114\text{ W}; (b) $\eta = 88.8%

NEXT STEPS
Final Takeaways from Your Teacher
  • Memorize the universal efficiency relation as η=What you get outWhat you put in\eta = \frac{\text{What you get out}}{\text{What you put in}}.

  • Perform a quick physical sanity check whenever you calculate efficiency to confirm it is strictly below 100%100\% for passive components.

Lock it in

Similar question

01

A step-down transformer has a primary voltage of 230 V (rms)230\text{ V (rms)} and draws 1.50 A (rms)1.50\text{ A (rms)} with a lagging power factor of 0.8500.850. The secondary supplies a purely resistive heating element with 24.0 V (rms)24.0\text{ V (rms)} at 11.5 A (rms)11.5\text{ A (rms)}. Calculate the transformer's efficiency η\eta.

Answer

Pin=VpIpcos⁡ϕp=230×1.50×0.850=293.25 WP_{\text{in}} = V_p I_p \cos\phi_p = 230 \times 1.50 \times 0.850 = 293.25\text{ W}. For a purely resistive load, Pout=VsIs=24.0×11.5=276.0 WP_{\text{out}} = V_s I_s = 24.0 \times 11.5 = 276.0\text{ W}. Efficiency η=276.0293.25×100%≈94.1%\eta = \frac{276.0}{293.25} \times 100\% \approx 94.1\%.

02

An industrial transformer operates at an efficiency of 92.0%92.0\%. The primary receives 480 V (rms)480\text{ V (rms)} at 12.5 A (rms)12.5\text{ A (rms)} with a phase angle of 25.0∘25.0^\circ. If the secondary load has a power factor of 0.9000.900 and an output voltage of 120 V (rms)120\text{ V (rms)}, what is the secondary current IsI_s?

Answer

Pin=(480)(12.5)cos⁡(25.0∘)≈5437.8 WP_{\text{in}} = (480)(12.5)\cos(25.0^\circ) \approx 5437.8\text{ W}. Real output power Pout=η⋅Pin=0.920×5437.8≈5002.8 WP_{\text{out}} = \eta \cdot P_{\text{in}} = 0.920 \times 5437.8 \approx 5002.8\text{ W}. Since Pout=VsIscos⁡ϕsP_{\text{out}} = V_s I_s \cos\phi_s, we have Is=5002.8120×0.900≈46.3 AI_s = \frac{5002.8}{120 \times 0.900} \approx 46.3\text{ A}.

03

A technician tests a non-ideal transformer. The primary meter reads Vp=100 VV_p = 100\text{ V}, Ip=4.00 AI_p = 4.00\text{ A}, and apparent power Sp=400 VAS_p = 400\text{ VA}. Core and copper losses consume 30.0 W30.0\text{ W} inside the transformer, and the secondary delivers 330 W330\text{ W} to a load. Determine (a) the primary power factor cos⁡ϕp\cos\phi_p and (b) the efficiency of the transformer.

Answer

(a) By energy conservation, total input real power is Pin=Pout+Ploss=330+30.0=360 WP_{\text{in}} = P_{\text{out}} + P_{\text{loss}} = 330 + 30.0 = 360\text{ W}. The power factor is cos⁡ϕp=PinSp=360 W400 VA=0.900\cos\phi_p = \frac{P_{\text{in}}}{S_p} = \frac{360\text{ W}}{400\text{ VA}} = 0.900. (b) Efficiency η=PoutPin×100%=330360×100%≈91.7%\eta = \frac{P_{\text{out}}}{P_{\text{in}}} \times 100\% = \frac{330}{360} \times 100\% \approx 91.7\%.