In a physics engineering laboratory, an AC generator test bench uses a multi-turn armature driven by a variable-speed motor inside a field created by electromagnets. The generator output feeds an experimental toroidal transformer to calibrate line losses. The data acquisition system records: primary input voltage , primary input current , and primary phase angle (current lags voltage). Across the secondary terminals, a precision digital power analyzer records a load voltage of across a purely resistive load box drawing . (a) Compute the real input power delivered to the transformer primary. (b) Determine the transformer efficiency under these experimental test bench conditions.
Answer and steps
Final answer
(a) ; (b)
Steps
Part (a): Real Input Power Delivered to the Primary
In an alternating current () circuit, real (average) power accounts for the phase difference between the voltage and current waveforms. The formula for the real input power is:
where:
- is the root-mean-square () primary voltage,
- is the primary current,
- is the phase angle by which the current lags the voltage,
- is the primary power factor.
Calculate the power factor:
Substitute the values:
Common Pitfall: Do not simply multiply . That gives the apparent power in volt-amperes (), which overestimates the useful real power entering an inductive or reactive component.
Part (b): Transformer Efficiency Under Test Conditions
-
Calculate the Output Power (): The secondary circuit is connected to a purely resistive load, meaning the voltage and current are in phase (, so ).
-
Calculate Efficiency (): The efficiency of the transformer is the ratio of real power delivered to the load to the real power supplied to the primary:
Substitute the values:
Typical errors
01 The student ignores the primary power factor cos(phi_p) and equates real input power to apparent power V_p * I_p, leading to an underestimated efficiency.
Sample Student Work
Reviewed by ACEpath TeacherStep-by-Step Review
Walk Through It with Your Teacher- Step 1Correct
In an AC circuit where current and voltage are out of phase, the product represents apparent power in volt-amperes, not real power. To find the real power delivered to the primary, you must multiply by the power factor .
- Step 2
- Step 3Correct
Your efficiency formula and division are mathematically sound, but using the incorrect input power of from Step 1 caused the resulting efficiency to be lower than the true value.
WHAT YOU DID WELL
Compliments from Your TeacherYou correctly recognized that the output load is purely resistive, making when finding .
You correctly applied the ratio formula for transformer efficiency, .
THE ERROR
Where Your ACEpath Teacher Spotted the Mistakeno
WHY IT HAPPENED
ACEpath Teacher's DiagnosisConfusing apparent power with real (active) power in reactive AC circuits.
REASONING PATH
Your ACEpath teacher’s suggested approach- Real Power vs. Apparent Power
Real power in single-phase AC is given by , where is the power factor.
Check if a phase angle or power factor is specified whenever an AC circuit contains inductive or capacitive elements.
- Transformer Primary Inductance
Transformer coils have inherent self-inductance and magnetizing currents that create a phase shift between primary voltage and current.
Always multiply the primary volt-amperes by when evaluating input real power unless a unity power factor is explicitly stated.
CORRECTED PATH
ACEpath Teacher's DemonstrationInclude the primary phase angle : .
Evaluate the real input power: .
Recalculate efficiency using the corrected real input power: .
(a) ; (b)
02 The student calculates the phase angle in radians while treating the numerical degree value as radians with sin(phi_p) instead of cos(phi_p), computing reactive power instead of real input power.
Sample Student Work
Reviewed by ACEpath TeacherStep-by-Step Review
Walk Through It with Your Teacher- Step 1Correct
Real (active) power in an AC circuit is determined by the power factor , not . Multiplying by calculates the reactive power in volt-amperes reactive (VAR), rather than the real power in watts.
- Step 2
- Step 3Correct
Your efficiency formula is conceptually correct, but substituting the incorrect reactive power for produced an unphysical efficiency over .
WHAT YOU DID WELL
Compliments from Your TeacherYou correctly calculated the secondary real output power for the resistive load.
You correctly stated the definition of efficiency as the ratio of output power to input power .
You accurately evaluated numerical arithmetic for the expressions you wrote.
THE ERROR
Where Your ACEpath Teacher Spotted the MistakeYou used instead of when calculating the input power.
WHY IT HAPPENED
ACEpath Teacher's DiagnosisYou confused active (real) power with reactive power . In AC circuit analysis, the in-phase component of current that produces useful real work is proportional to the cosine of the phase angle (the power factor).
REASONING PATH
Your ACEpath teacher’s suggested approach- Real Power vs. Reactive Power
Real power delivered is , while reactive power is .
Always associate real power (watts) with and reactive power (VAR) with .
- Conservation of Energy Sanity Check
For any passive electrical component or transformer, output power cannot exceed input power, meaning efficiency must satisfy .
If a computed efficiency exceeds , pause and re-examine whether input power was underestimated or calculated using reactive power.
CORRECTED PATH
ACEpath Teacher's Demonstration(a) ; (b)
03 The student calculates efficiency inverted as input power divided by output power, obtaining an efficiency greater than 100%.
Sample Student Work
Reviewed by ACEpath TeacherStep-by-Step Review
Walk Through It with Your Teacher- Step 1
- Step 2
- Step 3Correct
You placed input power in the numerator and output power in the denominator. Efficiency is always the ratio of useful output to total input, , which cannot exceed for a passive transformer.
WHAT YOU DID WELL
Compliments from Your TeacherYou correctly included the primary phase angle to calculate the real input power rather than apparent power.
You accurately calculated the secondary real power delivered to the resistive load.
THE ERROR
Where Your ACEpath Teacher Spotted the Mistakeno
WHY IT HAPPENED
ACEpath Teacher's DiagnosisYou defined efficiency as rather than , overlooking that conservation of energy requires the useful output power of a passive device to be less than or equal to the supplied input power.
REASONING PATH
Your ACEpath teacher’s suggested approach- Definition of Efficiency
Always verify that the useful output is in the numerator and the total input supplied is in the denominator.
- Sanity Check via Conservation of Energy
For any passive system with losses, , so .
If your calculated efficiency exceeds , check whether you inverted the ratio.
CORRECTED PATH
ACEpath Teacher's DemonstrationWrite the definition of efficiency: .
Substitute and : .
Evaluate the percentage: .
(a) ; (b) $\eta = 88.8%
Lock it in
What is the formula for the real (average) power absorbed by an AC load with rms voltage , rms current , and phase difference ?
. The factor is the power factor, accounting for the phase displacement between voltage and current.
Similar question
A step-down transformer has a primary voltage of and draws with a lagging power factor of . The secondary supplies a purely resistive heating element with at . Calculate the transformer's efficiency .
Answer
. For a purely resistive load, . Efficiency .
An industrial transformer operates at an efficiency of . The primary receives at with a phase angle of . If the secondary load has a power factor of and an output voltage of , what is the secondary current ?
Answer
. Real output power . Since , we have .
A technician tests a non-ideal transformer. The primary meter reads , , and apparent power . Core and copper losses consume inside the transformer, and the secondary delivers to a load. Determine (a) the primary power factor and (b) the efficiency of the transformer.
Answer
(a) By energy conservation, total input real power is . The power factor is . (b) Efficiency .