An industrial refrigeration chiller extracts heat at a rate of Q˙C=45.0 kJ/min\dot{Q}_C = 45.0\text{ kJ}/\text{min} from a cold-storage brine chamber maintained at tC=−15.0∘Ct_C = -15.0^\circ\text{C} and rejects thermal energy at a rate of Q˙H=68.0 kJ/min\dot{Q}_H = 68.0\text{ kJ}/\text{min} into ambient cooling water at tH=27.0∘Ct_H = 27.0^\circ\text{C}. Convert all quantities into coherent SI base units (Kelvin and Watts), and calculate: (a) the electrical power input W˙in\dot{W}_{\text{in}} supplied to the compressor in Watts, (b) the actual coefficient of performance COPactual\text{COP}_{\text{actual}}, and (c) the rate of total entropy generation S˙gen\dot{S}_{\text{gen}} in the universe in W/K\text{W}/\text{K}.

Answer and steps

Final answer

(a) W˙in=383 W\dot{W}_{\text{in}} = 383\text{ W}; (b) COPactual=1.96\text{COP}_{\text{actual}} = 1.96; (c) S˙gen=+0.871 W/K\dot{S}_{\text{gen}} = +0.871\text{ W}/\text{K}

Steps

01

Convert Given Quantities to SI Base Units

Convert the temperatures from degrees Celsius to Kelvin: TC=−15.0+273.15=258.15 KT_C = -15.0 + 273.15 = 258.15\text{ K} TH=27.0+273.15=300.15 KT_H = 27.0 + 273.15 = 300.15\text{ K}

Convert the heat flow rates from kilojoules per minute to Watts (J/s\text{J}/\text{s}): Q˙C=45.0 kJmin=45.0×103 J60 s=750 W\dot{Q}_C = \frac{45.0\text{ kJ}}{\text{min}} = \frac{45.0 \times 10^3\text{ J}}{60\text{ s}} = 750\text{ W} Q˙H=68.0 kJmin=68.0×103 J60 s=34003 W≈1133.33 W\dot{Q}_H = \frac{68.0\text{ kJ}}{\text{min}} = \frac{68.0 \times 10^3\text{ J}}{60\text{ s}} = \frac{3400}{3}\text{ W} \approx 1133.33\text{ W}


02

(a) Determine the Power Input to the Compressor

Applying the first law of thermodynamics (energy conservation) to the chiller operating in a steady cycle: W˙in+Q˙C=Q˙H\dot{W}_{\text{in}} + \dot{Q}_C = \dot{Q}_H

Rearranging for the compressor power input W˙in\dot{W}_{\text{in}}: W˙in=Q˙H−Q˙C=1133.33 W−750 W≈383.33 W\dot{W}_{\text{in}} = \dot{Q}_H - \dot{Q}_C = 1133.33\text{ W} - 750\text{ W} \approx 383.33\text{ W}

Rounding to three significant figures: W˙in≈383 W\dot{W}_{\text{in}} \approx 383\text{ W}


03

(b) Calculate the Coefficient of Performance (COPactual\text{COP}_{\text{actual}})

The coefficient of performance for a refrigeration cycle measures the desired cooling effect per unit of work supplied: COPactual=Q˙CW˙in\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}}

Substitute the unrounded values: COPactual=750 W383.33 W≈1.9565\text{COP}_{\text{actual}} = \frac{750\text{ W}}{383.33\text{ W}} \approx 1.9565

Rounding to three significant figures: COPactual≈1.96\text{COP}_{\text{actual}} \approx 1.96

Common Pitfall: Do not use the Carnot refrigeration formula COPrev=TCTH−TC\text{COP}_{\text{rev}} = \frac{T_C}{T_H - T_C} here. That expression represents the theoretical maximum efficiency of a reversible cycle, whereas real industrial chillers have internal irreversibilities and lower actual performance.


04

(c) Calculate the Total Entropy Generation Rate (S˙gen\dot{S}_{\text{gen}})

For a continuous, steady-state cyclic device, the state of the working fluid does not change over complete cycles (ΔSsystem=0\Delta S_{\text{system}} = 0). Therefore, the entropy generated in the universe equals the net change in entropy of the thermal reservoirs:

S˙gen=ΔS˙univ=S˙H+S˙C\dot{S}_{\text{gen}} = \Delta \dot{S}_{\text{univ}} = \dot{S}_{H} + \dot{S}_{C}

Heat leaves the cold chamber and enters the ambient water: S˙C=−Q˙CTC=−750 W258.15 K≈−2.9053 W/K\dot{S}_C = -\frac{\dot{Q}_C}{T_C} = -\frac{750\text{ W}}{258.15\text{ K}} \approx -2.9053\text{ W}/\text{K} S˙H=+Q˙HTH=+1133.33 W300.15 K≈+3.7759 W/K\dot{S}_H = +\frac{\dot{Q}_H}{T_H} = +\frac{1133.33\text{ W}}{300.15\text{ K}} \approx +3.7759\text{ W}/\text{K}

Combining the two rates: S˙gen=Q˙HTH−Q˙CTC=3.7759 W/K−2.9053 W/K≈+0.8706 W/K\dot{S}_{\text{gen}} = \frac{\dot{Q}_H}{T_H} - \frac{\dot{Q}_C}{T_C} = 3.7759\text{ W}/\text{K} - 2.9053\text{ W}/\text{K} \approx +0.8706\text{ W}/\text{K}

Rounding to three significant figures: S˙gen≈+0.871 W/K\dot{S}_{\text{gen}} \approx +0.871\text{ W}/\text{K}

Because the process is irreversible, the Second Law of Thermodynamics requires S˙gen>0\dot{S}_{\text{gen}} > 0, which aligns with our positive result.

Typical errors

OverviewACEpath Teacher's Diagnosis

01 The student calculates COP using the heat rejected to the ambient cooling water Q_dot_H instead of the cooling capacity Q_dot_C.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Q˙C=4500060=750 W  ⟹  Q˙H=6800060=1133.33 W  ⟹  W˙in=Q˙H−Q˙C=1133.33−750=383.33 W\dot{Q}_C = \frac{45000}{60} = 750\text{ W} \implies \dot{Q}_H = \frac{68000}{60} = 1133.33\text{ W} \implies \dot{W}_{\text{in}} = \dot{Q}_H - \dot{Q}_C = 1133.33 - 750 = 383.33\text{ W}

  2. Step 2

    COP=Q˙HW˙in  ⟹  COP=1133.33383.33=2.96\text{COP} = \frac{\dot{Q}_H}{\dot{W}_{\text{in}}} \implies \text{COP} = \frac{1133.33}{383.33} = 2.96

    Correct

    COPactual=Q˙CW˙in=750 W383.33 W≈1.96\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{750\text{ W}}{383.33\text{ W}} \approx 1.96

    You defined the coefficient of performance using heat rejected to the warm environment Q˙H\dot{Q}_H, which corresponds to a heat pump. For a refrigerator or chiller, the desired cooling effect is the heat removed from the cold chamber, Q˙C\dot{Q}_C.

  3. Step 3

    TC=−15.0+273.15=258.15 K  ⟹  TH=27.0+273.15=300.15 K  ⟹  S˙gen=1133.33300.15−750258.15=0.871 W/KT_C = -15.0 + 273.15 = 258.15\text{ K} \implies T_H = 27.0 + 273.15 = 300.15\text{ K} \implies \dot{S}_{\text{gen}} = \frac{1133.33}{300.15} - \frac{750}{258.15} = 0.871\text{ W}/\text{K}

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly converted heat rates from kilojoules per minute to Watts.

You applied the First Law of Thermodynamics to calculate the compressor power input.

You correctly converted temperatures to absolute Kelvin and evaluated the universe's entropy generation rate.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
COP definition mix-up (refrigerator vs. heat pump)

no

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You used the heat pump definition COP=Q˙HW˙in\text{COP} = \frac{\dot{Q}_H}{\dot{W}_{\text{in}}} rather than the refrigeration definition COP=Q˙CW˙in\text{COP} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}}, confusing the desired thermal effect of a chiller with that of a heating device.

REASONING PATH
Your ACEpath teacher’s suggested approach
Identify the Desired Output
  • COP=Desired OutputRequired Work Input\text{COP} = \frac{\text{Desired Output}}{\text{Required Work Input}}

  • Always identify the goal of the device: for a refrigerator/chiller, the goal is cooling (Q˙C\dot{Q}_C); for a heat pump, the goal is heating (Q˙H\dot{Q}_H).

Heat Pump vs. Refrigerator Relation
  • COPHP=COPR+1\text{COP}_{\text{HP}} = \text{COP}_{\text{R}} + 1

  • Notice that your value of 2.962.96 is exactly 1+1.961 + 1.96, which confirms that you calculated COPHP\text{COP}_{\text{HP}} instead of COPR\text{COP}_{\text{R}}.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Identify the desired cooling rate: Q˙C=750 W\dot{Q}_C = 750\text{ W}.

  2. Substitute Q˙C\dot{Q}_C and W˙in\dot{W}_{\text{in}} into the refrigeration performance definition: COPactual=Q˙CW˙in=750 W383.33 W\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{750\text{ W}}{383.33\text{ W}}.

  3. Evaluate the ratio: COPactual≈1.96\text{COP}_{\text{actual}} \approx 1.96.

Final answer

(a) W˙in=383 W\dot{W}_{\text{in}} = 383\text{ W}; (b) COPactual=1.96\text{COP}_{\text{actual}} = 1.96; (c) S˙gen=+0.871 W/K\dot{S}_{\text{gen}} = +0.871\text{ W}/\text{K}

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the fundamental distinction between refrigeration cycles (maximizing Q˙C\dot{Q}_C) and heat pump cycles (maximizing Q˙H\dot{Q}_H).

  • Double-check that the numerator of any COP formula matches the specific thermal objective stated in the problem prompt.

OverviewACEpath Teacher's Diagnosis

02 The student uses Celsius temperatures instead of absolute temperatures in Kelvin when calculating the rate of entropy generation.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Q˙C=45000 J/60 s=750 W  ⟹  Q˙H=68000 J/60 s=1133.33 W  ⟹  W˙in=1133.33−750=383.33 W\dot{Q}_C = 45000\text{ J}/60\text{ s} = 750\text{ W} \implies \dot{Q}_H = 68000\text{ J}/60\text{ s} = 1133.33\text{ W} \implies \dot{W}_{\text{in}} = 1133.33 - 750 = 383.33\text{ W}

  2. Step 2

    COP=Q˙CW˙in=750383.33=1.96\text{COP} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{750}{383.33} = 1.96

  3. Step 3

    S˙gen=Q˙HtH−Q˙CtC=1133.3327.0−750(−15.0)=41.98−(−50.0)=91.98 W/K\dot{S}_{\text{gen}} = \frac{\dot{Q}_H}{t_H} - \frac{\dot{Q}_C}{t_C} = \frac{1133.33}{27.0} - \frac{750}{(-15.0)} = 41.98 - (-50.0) = 91.98\text{ W}/\text{K}

    Correct

    S˙gen=Q˙HTH−Q˙CTC=1133.33 W300.15 K−750 W258.15 K≈0.871 W/K\dot{S}_{\text{gen}} = \frac{\dot{Q}_H}{T_H} - \frac{\dot{Q}_C}{T_C} = \frac{1133.33\text{ W}}{300.15\text{ K}} - \frac{750\text{ W}}{258.15\text{ K}} \approx 0.871\text{ W}/\text{K}

    You set up the correct net reservoir entropy balance, but you used Celsius temperatures (tH=27.0∘Ct_H = 27.0^\circ\text{C} and tC=−15.0∘Ct_C = -15.0^\circ\text{C}) in the denominator. Thermodynamic entropy definitions require absolute temperatures in Kelvin (T=t+273.15T = t + 273.15).

WHAT YOU DID WELL
Compliments from Your Teacher

You correctly converted heat rates from kilojoules per minute to Watts.

You applied energy conservation around the steady cycle to determine the required power input.

You used the definition of actual refrigeration COP and obtained the correct numerical value.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Thermodynamic temperature unit error

You substituted values measured in degrees Celsius into an entropy transfer relation that strictly requires absolute temperature.

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

Thermodynamic entropy transfer across a reservoir boundary is defined as dS=δQTdS = \frac{\delta Q}{T}, where TT is the absolute thermodynamic temperature. Because the absolute zero point is 0 K0\text{ K} (not 0∘C0^\circ\text{C}), temperatures must be shifted by +273.15+273.15 whenever temperature appears as an absolute denominator rather than as a temperature difference ΔT\Delta T.

REASONING PATH
Your ACEpath teacher’s suggested approach
Absolute Temperature Requirement
  • Any thermodynamic relation containing temperature outside of a difference ΔT\Delta T requires the absolute scale: T(K)=t(∘C)+273.15T(\text{K}) = t(^\circ\text{C}) + 273.15.

  • Always convert all given reservoir temperatures to Kelvin before evaluating entropy changes or efficiency limits.

Sign-Check on Entropy of Heat Extraction
  • Removing heat from a positive absolute temperature reservoir must decrease that reservoir's entropy: ΔS=−QT<0\Delta S = -\frac{Q}{T} < 0.

  • Notice that dividing by negative Celsius temperatures falsely inverts the sign of entropy changes.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Convert the reservoir temperatures to Kelvin: TC=−15.0+273.15=258.15 KT_C = -15.0 + 273.15 = 258.15\text{ K} and TH=27.0+273.15=300.15 KT_H = 27.0 + 273.15 = 300.15\text{ K}.

  2. Write the entropy rate balance for the universe: S˙gen=ΔS˙univ=Q˙HTH−Q˙CTC\dot{S}_{\text{gen}} = \Delta \dot{S}_{\text{univ}} = \frac{\dot{Q}_H}{T_H} - \frac{\dot{Q}_C}{T_C}.

  3. Substitute the absolute temperatures: S˙gen=1133.33 W300.15 K−750 W258.15 K≈3.7759 W/K−2.9053 W/K=0.8706 W/K\dot{S}_{\text{gen}} = \frac{1133.33\text{ W}}{300.15\text{ K}} - \frac{750\text{ W}}{258.15\text{ K}} \approx 3.7759\text{ W}/\text{K} - 2.9053\text{ W}/\text{K} = 0.8706\text{ W}/\text{K}.

Final answer

(a) W˙in=383 W\dot{W}_{\text{in}} = 383\text{ W}; (b) COPactual=1.96\text{COP}_{\text{actual}} = 1.96; (c) S˙gen=+0.871 W/K\dot{S}_{\text{gen}} = +0.871\text{ W}/\text{K}

NEXT STEPS
Final Takeaways from Your Teacher
  • Always write temperature conversions (T=t+273.15 KT = t + 273.15\text{ K}) in your initial setup block before writing formula ratios.

  • Check whether temperature appears as a bare state variable (TT) or as a difference (ΔT\Delta T) to decide if unit shifting is mandatory.

  • Practice evaluating reservoir entropy changes for refrigeration and heat-pump cycles using consistent Kelvin units.

OverviewACEpath Teacher's Diagnosis

03 The student calculates the theoretical Carnot COP instead of the actual COP requested by the problem.

Sample Student Work

Reviewed by ACEpath Teacher
Step-by-Step Review
Walk Through It with Your Teacher
Partially correct
  1. Step 1

    Q˙C=4500060=750 W  ⟹  Q˙H=6800060=1133.33 W  ⟹  W˙in=1133.33−750=383.33 W\dot{Q}_C = \frac{45000}{60} = 750\text{ W} \implies \dot{Q}_H = \frac{68000}{60} = 1133.33\text{ W} \implies \dot{W}_{\text{in}} = 1133.33 - 750 = 383.33\text{ W}

  2. Step 2

    TC=−15.0+273.15=258.15 K  ⟹  TH=27.0+273.15=300.15 K  ⟹  COP=TCTH−TC=258.15300.15−258.15=258.1542.0=6.15T_C = -15.0 + 273.15 = 258.15\text{ K} \implies T_H = 27.0 + 273.15 = 300.15\text{ K} \implies \text{COP} = \frac{T_C}{T_H - T_C} = \frac{258.15}{300.15 - 258.15} = \frac{258.15}{42.0} = 6.15

    Correct

    COPactual=Q˙CW˙in=750 W383.33 W≈1.96\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{750\text{ W}}{383.33\text{ W}} \approx 1.96

    You used the Carnot formula COP=TCTH−TC\text{COP} = \frac{T_C}{T_H - T_C}, which gives the maximum theoretical performance of a reversible refrigerator. For an actual cycle with irreversibilities, COP is defined by the ratio of actual cooling rate to power input: COPactual=Q˙CW˙in\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}}.

  3. Step 3

    S˙gen=1133.33300.15−750258.15=0.871 W/K\dot{S}_{\text{gen}} = \frac{1133.33}{300.15} - \frac{750}{258.15} = 0.871\text{ W/K}

WHAT YOU DID WELL
Compliments from Your Teacher

You converted minutes to seconds and Celsius to Kelvin without any arithmetic slips.

You applied the First Law energy balance correctly to obtain W˙in=383 W\dot{W}_{\text{in}} = 383\text{ W}.

You set up and calculated the entropy generation rate S˙gen\dot{S}_{\text{gen}} with proper reservoir signs and units.

THE ERROR
Where Your ACEpath Teacher Spotted the Mistake
Carnot COP vs. Actual COP Confusion

none

WHY IT HAPPENED
ACEpath Teacher's Diagnosis

You conflated the theoretical upper limit (extCOPrev ext{COP}_{\text{rev}}, determined solely by reservoir temperatures) with the real device performance (extCOPactual ext{COP}_{\text{actual}}, determined by the actual energy flows Q˙C/W˙in\dot{Q}_C / \dot{W}_{\text{in}}).

REASONING PATH
Your ACEpath teacher’s suggested approach
Check which COP is requested
  • For any real or irreversible refrigeration cycle, COPactual=Q˙CW˙in\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}}. The temperature formula TCTH−TC\frac{T_C}{T_H - T_C} applies only to a reversible Carnot cycle.

  • Always compute COPactual\text{COP}_{\text{actual}} from the actual heat removed divided by the work supplied unless the problem states the cycle is reversible or asks for the Carnot maximum.

CORRECTED PATH
ACEpath Teacher's Demonstration
  1. Identify the desired cooling rate: Q˙C=750 W\dot{Q}_C = 750\text{ W}.

  2. Identify the actual power consumed: W˙in=383.33 W\dot{W}_{\text{in}} = 383.33\text{ W}.

  3. Compute COPactual=Q˙CW˙in=750 W383.33 W≈1.96\text{COP}_{\text{actual}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{750\text{ W}}{383.33\text{ W}} \approx 1.96.

Final answer

(a) W˙in=383 W\dot{W}_{\text{in}} = 383\text{ W}; (b) COPactual=1.96\text{COP}_{\text{actual}} = 1.96; (c) S˙gen=+0.871 W/K\dot{S}_{\text{gen}} = +0.871\text{ W/K}

NEXT STEPS
Final Takeaways from Your Teacher
  • Review the distinction between ideal (Carnot) thermodynamic performance and actual performance for heat pumps and refrigerators.

  • Practice identifying whether a question supplies enough heat/work data to compute actual efficiency or if it asks for the theoretical Carnot bound.

Lock it in

Similar question

01

A domestic refrigerator absorbs heat from its freezer compartment at a rate of 1.20 kW1.20\text{ kW} and discharges heat to the kitchen at a rate of 1.60 kW1.60\text{ kW}. Calculate the electrical power input to the compressor and the refrigerator's COP.

Answer

W˙in=Q˙H−Q˙C=1.60 kW−1.20 kW=0.40 kW=400 W\dot{W}_{\text{in}} = \dot{Q}_H - \dot{Q}_C = 1.60\text{ kW} - 1.20\text{ kW} = 0.40\text{ kW} = 400\text{ W}. The COP of the refrigerator is COPR=Q˙CW˙in=1.20 kW0.40 kW=3.00\text{COP}_{\text{R}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{1.20\text{ kW}}{0.40\text{ kW}} = 3.00.

02

An air-conditioning unit maintains a room at 21.0∘C21.0^\circ\text{C} while outside ambient air is at 35.0∘C35.0^\circ\text{C}. The unit extracts 5.00 kW5.00\text{ kW} of heat from the room with an actual COP of 2.502.50. (a) Determine the required power input W˙in\dot{W}_{\text{in}}. (b) Determine the rate of heat rejection Q˙H\dot{Q}_H to the outside.

Answer

(a) W˙in=Q˙CCOP=5.00 kW2.50=2.00 kW\dot{W}_{\text{in}} = \frac{\dot{Q}_C}{\text{COP}} = \frac{5.00\text{ kW}}{2.50} = 2.00\text{ kW}. (b) By energy conservation, Q˙H=Q˙C+W˙in=5.00 kW+2.00 kW=7.00 kW\dot{Q}_H = \dot{Q}_C + \dot{W}_{\text{in}} = 5.00\text{ kW} + 2.00\text{ kW} = 7.00\text{ kW}.

03

A water chiller operates steadily between a cold reservoir at tC=4.0∘Ct_C = 4.0^\circ\text{C} and a warm reservoir at tH=32.0∘Ct_H = 32.0^\circ\text{C}. It removes heat at a rate of Q˙C=12.0 kW\dot{Q}_C = 12.0\text{ kW} with a compressor power input of W˙in=4.00 kW\dot{W}_{\text{in}} = 4.00\text{ kW}. (a) Find the actual COPR\text{COP}_{\text{R}}. (b) Calculate the rate of entropy generation in the universe, S˙gen\dot{S}_{\text{gen}}, in W/K\text{W}/\text{K}.

Answer

(a) COPR=Q˙CW˙in=12.0 kW4.00 kW=3.00\text{COP}_{\text{R}} = \frac{\dot{Q}_C}{\dot{W}_{\text{in}}} = \frac{12.0\text{ kW}}{4.00\text{ kW}} = 3.00. (b) Heat rejected: Q˙H=12.0+4.00=16.0 kW=16000 W\dot{Q}_H = 12.0 + 4.00 = 16.0\text{ kW} = 16000\text{ W}. Absolute temperatures: TC=4.0+273.15=277.15 KT_C = 4.0 + 273.15 = 277.15\text{ K}, TH=32.0+273.15=305.15 KT_H = 32.0 + 273.15 = 305.15\text{ K}. Rate of entropy generation: S˙gen=Q˙HTH−Q˙CTC=16000305.15−12000277.15≈52.433−43.298=+9.14 W/K\dot{S}_{\text{gen}} = \frac{\dot{Q}_H}{T_H} - \frac{\dot{Q}_C}{T_C} = \frac{16000}{305.15} - \frac{12000}{277.15} \approx 52.433 - 43.298 = +9.14\text{ W}/\text{K}.